18
10.3. Indoor Unit
10.3.1.
HOW TO FIX INSTALLATION PLATE
The mounting wall is strong and solid enough to prevent it from
the vibration.
The centre of installation plate should be at more than 680 mm
at right and 570 mm at left of the wall.
The distance from installation plate edge to ceiling should more
than 73 mm.
From installation plate left edge to unit’s left side is 20 mm.
From installation plate right edge to unit’s right is 130 mm.
1. Mount the installation plate on the wall with 5 screws or
more.
(If mounting the unit on the concrete wall, consider using
anchor bolts.)
• Always mount the installation plate horizontally by
aligning the marking-off line with the thread and using a
level gauge.
2. Drill the piping plate hole with ø70 mm hole-core drill.
• Line according to the arrows marked on the lower left
and right side of the installation plate. The meeting point
of the extended line is the centre of the hole. Another
method is by putting measuring tape at position as
shown in the diagram above. The hole centre is obtained
by measuring the distance namely 140 mm and 155 mm
for left and right hole respectively.
• Drill the piping hole at either the right or the left and the
hole should be slightly slanted to the outdoor side.
10.3.2.
TO DRILL A HOLE IN THE WALL
AND INSTALL A SLEEVE OF
PIPING
1. Insert the piping sleeve to the hole.
2. Fix the bushing to the sleeve.
3. Cut the sleeve until it extrudes about 15 mm from the
wall.
4. Finish by sealing the sleeve with putty or caulking
compound at the final stage.
10.3.3.
INDOOR UNIT INSTALLATION
1. For the right rear piping
2. For the right and right bottom piping
: For left side piping, piping connection for liquid should be about
155 mm from this line.
: For left side piping, piping connection for gas should be about
190 mm from this line.
: For left side piping, piping connection cable should be about
1100 mm from this line.
Caution
When the wall is hollow, please be sure to use the
sleeve for tube ass’y to prevent dangers caused by
mice biting the connecting cable.
Summary of Contents for CS-V28EKE CU-V28EKE
Page 8: ...8 4 Location of Controls and Components Indoor Unit Outdoor Unit Remote Control ...
Page 9: ...9 5 Dimensions 5 1 Indoor Unit Remote Control ...
Page 10: ...10 5 2 Outdoor Unit ...
Page 11: ...11 6 Refrigeration Cycle Diagram ...
Page 12: ...12 7 Block Diagram ...
Page 13: ...13 8 Wiring Connection Diagram ...
Page 14: ...14 9 Printed Circuit Board 9 1 Indoor Unit BOTTOM VIEW ...
Page 15: ...15 TOP VIEW ...
Page 16: ...16 9 2 Indicator And Receiver BOTTOM VIEW TOP VIEW ...
Page 20: ...20 This can be used for left rear piping and left bottom piping also ...
Page 43: ...43 15 Technical Data 15 1 Thermostat Characteristics ...
Page 45: ...45 15 3 Operation Characteristics 15 3 1 CS V28EKE CU V28EKE ...
Page 46: ...46 ...