14.4.8 H25 (e-ion Air Purifying System Abnormal)
Malfunction Decision Conditions
•
During standby of cooling and heating operation, e-ion breakdown occurs and air conditioner stops operation.
Malfunction Caused
•
Faulty indoor main PCB.
•
Faulty indoor e-ion power module.
Troubleshooting
For safety reason and to prevent component
breakdown, always switch off the power
before remove and connect the component.
When abnormality indication starts again
•
Turn off the power, and reconnect CN-CLN connector
•
Turn on the power, and measure again the DC voltage
between CN-CLN channel 4 & 2
Is the voltage measured at 5Vdc?
•
Defect in indoor unit e-ion power module
•
Replace the indoor unit e-ion power module
•
Defect in indoor unit main PCB
•
Replace the indoor unit main PCB
Check the indoor unit main PCB CN-CLN terminal 4 & 2 DC
voltage:
•
Turn off the power
•
Disconnect the CN-CLN connector
•
Turn on the power, measure the DC voltage between
CN-CLN terminal 4 & 2
Is the DC voltage measured at 5Vdc?
NO
•
Defect in indoor main PCB
•
Replace the indoor unit main PCB
YES
NO
YES
E-ion power
module
Summary of Contents for CS-PS9JKT
Page 7: ...7 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control...
Page 8: ...8 4 Dimensions 4 1 Indoor Unit...
Page 10: ...10 5 Refrigeration Cycle Diagram...
Page 11: ...11 6 Block Diagram 6 1 CS PS9JKT CU PS9JKT...
Page 12: ...12 6 2 CS PS12JKT CU PS12JKT...
Page 13: ...13 7 Wiring Connection Diagram 7 1 Indoor Unit...
Page 14: ...14 7 2 Outdoor Unit 7 2 1 CU PS9JKT...
Page 15: ...15 7 2 2 CU PS12JKT...
Page 16: ...16 8 Electronic Circuit Diagram 8 1 Indoor Unit...
Page 17: ...17 8 2 Outdoor Unit 8 2 1 CU PS9JKT...
Page 18: ...18 8 2 2 CU PS12JKT...
Page 21: ...21 9 2 Outdoor Unit 9 3 Main Printed Circuit Board 9 3 1 CU PS9JKT...
Page 22: ...22...
Page 23: ...23 9 3 2 CU PS12JKT...