14.4.17 F91 (Refrigeration Cycle Abnormality)
Malfunction Decision Conditions
•
During cooling, compressor frequency = Fcmax.
•
During cooling and heating operation, running current: 0.65A < I < 1.65A.
•
During cooling, indoor intake - indoor pipe < 4°C
Malfunction Caused
•
Refrigerant shortage (refrigerant leakage)
•
Poor compression performance of compressor.
•
2/3 way valve closed.
•
Detection error due to faulty indoor intake air or indoor pipe temperature sensors.
Troubleshooting
2/3-way valve opened?
Oil oozing out from the 2/3 way valve?
•
Replace the capillary tube or dryer.
When F91 indication happens
For safety reason and to prevent component
breakdown, always switch off the power
before remove and connect the component.
Check the indoor air intake and pipe
temperature sensors.
•
Open 2/3 way valve
Check for gas leaking.
•
Repair the pipe flare or union nuts.
Reclaim and recharge refrigerant.
NO
NO
YES
YES
Does it conform to the sensor
characteristic chart?
•
Replace the indoor intake air or pipe
temperature sensor
NO
Capillary tube or dryer clogged?
Charge for a specified amount of fresh
refrigerant.
YES
Refrigerant cycle abnormality error again?
•
Replace outdoor unit PCB &
compressor
NO
YES
•
Procedure
complete
Summary of Contents for CS-PS9JKT
Page 7: ...7 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control...
Page 8: ...8 4 Dimensions 4 1 Indoor Unit...
Page 10: ...10 5 Refrigeration Cycle Diagram...
Page 11: ...11 6 Block Diagram 6 1 CS PS9JKT CU PS9JKT...
Page 12: ...12 6 2 CS PS12JKT CU PS12JKT...
Page 13: ...13 7 Wiring Connection Diagram 7 1 Indoor Unit...
Page 14: ...14 7 2 Outdoor Unit 7 2 1 CU PS9JKT...
Page 15: ...15 7 2 2 CU PS12JKT...
Page 16: ...16 8 Electronic Circuit Diagram 8 1 Indoor Unit...
Page 17: ...17 8 2 Outdoor Unit 8 2 1 CU PS9JKT...
Page 18: ...18 8 2 2 CU PS12JKT...
Page 21: ...21 9 2 Outdoor Unit 9 3 Main Printed Circuit Board 9 3 1 CU PS9JKT...
Page 22: ...22...
Page 23: ...23 9 3 2 CU PS12JKT...