14.4.13 H98 (Indoor High Pressure Protection)
Error Code will not display (no Timer LED blinking) but store in EEPROM
Malfunction Decision Conditions
•
During heating operation, the temperature detected by the indoor pipe temperature sensor is above 60°C.
Malfunction Caused
•
Clogged air filter of the indoor unit
•
Dust accumulation on the indoor unit heat exchanger
•
Air short circuit
•
Detection error due to faulty indoor pipe temperature sensor
•
Detection error due to faulty indoor unit PCB
Troubleshooting
When abnormality indication starts again
Is the air filter dirty?
•
Clean the air filter
Check the indoor unit air filter
Is the indoor unit heat exchanger dirty?
•
Clean the indoor unit heat exchanger
Check the dust accumulation on the indoor unit heat exchanger
Does it conform to the sensor characteristic chart?
Check the indoor pipe temperature sensor
•
Replace the indoor pipe temperature
sensor
•
Replace the indoor unit PCB
YES
NO
NO
NO
YES
For safety reason and to prevent
component breakdown, always switch
off the power before remove and
connect the component.
Check the air passage
Is there any short circuit?
•
Provide sufficient air passage
YES
Summary of Contents for CS-PS9JKT
Page 7: ...7 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control...
Page 8: ...8 4 Dimensions 4 1 Indoor Unit...
Page 10: ...10 5 Refrigeration Cycle Diagram...
Page 11: ...11 6 Block Diagram 6 1 CS PS9JKT CU PS9JKT...
Page 12: ...12 6 2 CS PS12JKT CU PS12JKT...
Page 13: ...13 7 Wiring Connection Diagram 7 1 Indoor Unit...
Page 14: ...14 7 2 Outdoor Unit 7 2 1 CU PS9JKT...
Page 15: ...15 7 2 2 CU PS12JKT...
Page 16: ...16 8 Electronic Circuit Diagram 8 1 Indoor Unit...
Page 17: ...17 8 2 Outdoor Unit 8 2 1 CU PS9JKT...
Page 18: ...18 8 2 2 CU PS12JKT...
Page 21: ...21 9 2 Outdoor Unit 9 3 Main Printed Circuit Board 9 3 1 CU PS9JKT...
Page 22: ...22...
Page 23: ...23 9 3 2 CU PS12JKT...