44
9.7.7.
Sensor Disconnection Detection Control
• The sensor disconnection detection control activates when the following condition comply:
• During sensor disconnection, sensor error is displayed; all operations stops except outdoor fan remaining heat removal control.
9.7.8.
Valve Error Detection Control
• This control is to protect the compressor.
• Valve error is detected if comply with condition below:
- Power is on for the first time and within 5 minutes from compressor starts (However, the unit is considered power on for first
time when compressor starts operating continuously for 7 minutes).
- Indoor heat exchanger temperature at compressor start -3°C < current heat exchanger temperature for 1 minutes.
• During this error, four-way valve error is displayed; compressor is shutdown.
9.7.9.
High-pressure Switch Disconnection Error Detection Control
• High-pressure switch disconnection is detected when high-pressure switch input continuously open for 1 minutes while the
compressor shutdown.
• During this error, high-pressure switch error is displayed.
9.7.10.
Low-pressure Switch Disconnection Error Detection Control
• Low-pressure switch disconnection is detected when low-pressure switch input continuously open for 1 minutes while
compressor shutdown.
• During this error, low-pressure switch error is displayed.
9.8.
Test Run
• Test run is necessary after installation is completed.
• To enable forced cooling test run, at outdoor PCB, set the DS1 to ON position and DS2 to OFF position.
• Press Test Run button at outdoor pcb for 1 second.
Sensor
Detection Threshold
Duration (Sec.)
Detection Condition
Discharge Temperature
< -4.5
°
C or 201.8
°
C
5
Other than compressor start control
and compressor ON
Outdoor Heat Exchanger
< -50.5
°
C or 103.7
°
C
5
Regularly
Summary of Contents for CS-F24DTE5
Page 18: ...18 4 Dimensions 4 1 CS F24DTE5 CS F28DTE5 ...
Page 19: ...19 4 2 CS F34DTE5 CS F43DTE5 CS F50DTE5 ...
Page 20: ...20 4 3 CU J24DBE5 CU J24DBE8 CU J28DBE5 CU J28DBE8 ...
Page 21: ...21 4 4 CU J34DBE5 CU J34DBE8 CU J43DBE8 CU J50DBE8 ...
Page 23: ...23 5 2 CS F34DTE5 CU J34DBE5 CU J34DBE8 CS F43DTE5 CU J43DBE8 CS F50DTE5 CU J50DBE8 ...
Page 25: ...25 6 3 CU J34DBE5 6 4 CU J24DBE8 CU J28DBE8 6 5 CU J34DBE8 CU J43DBE8 CU J50DBE8 ...
Page 26: ...26 7 Wiring Diagram 7 1 CS F24DTE5 CS F28DTE5 CS F34DTE5 CS F43DTE5 CS F50DTE5 ...
Page 27: ...27 7 2 CU J24DBE5 CU J28DBE5 ...
Page 28: ...28 7 3 CU J34DBE5 ...
Page 29: ...29 7 4 CU J24DBE8 CU J28DBE8 ...
Page 30: ...30 7 5 CU J34DBE8 CU J43DBE8 CU J50DBE8 ...
Page 32: ...32 8 2 Remote Control Display ...
Page 33: ...33 8 3 Remote Control Panel ...
Page 116: ...116 13 4 Sound data ...
Page 117: ...117 ...
Page 118: ...118 ...
Page 119: ...119 ...
Page 120: ...120 ...
Page 121: ...121 13 5 Sound measuring point 13 5 1 Indoor Unit 13 5 2 Outdoor Unit ...
Page 127: ...127 14 Exploded View Indoor Unit 14 1 CS F24DTE5 CS F28DTE5 ...
Page 128: ...128 14 2 CS F24DTE5 CS F28DTE5 ...
Page 129: ...129 14 3 CS F24DTE5 CS F28DTE5 ...
Page 132: ...132 16 Exploded View Indoor Unit 16 1 CS F34DTE5 CS F43DTE5 CS F50DTE5 ...
Page 133: ...133 16 2 CS F34DTE5 CS F43DTE5 CS F50DTE5 ...
Page 134: ...134 16 3 CS F34DTE5 CS F43DTE5 CS F50DTE5 ...
Page 137: ...137 18 Exploded View Outdoor Unit 18 1 CU J24DBE5 CU J24DBE8 CU J28DBE5 CU J28DBE8 ...
Page 138: ...138 18 2 CU J24DBE5 CU J24DBE8 CU J28DBE5 CU J28DBE8 ...
Page 140: ...140 20 Exploded View Outdoor Unit 20 1 CU J34DBE5 CU J34DBE8 CU J43DBE8 CU J50DBE8 ...
Page 141: ...141 20 2 CU J34DBE5 CU J34DBE8 CU J43DBE8 CU J50DBE8 ...
Page 142: ...142 20 3 CU J34DBE5 CU J34DBE8 CU J43DBE8 CU J50DBE8 ...
Page 144: ...144 22 Print Pattern 22 1 Indoor Unit Printed Main ...