12.6. Self-diagnosis error code table
•
The display screen on the wired remote control unit and the self-diagnosis LEDs (red) on the outdoor unit printed circuit board
in the outdoor unit can be used to indicate where the location of a problem is.
Refer to the table below to remove the cause of the problem, and then re-start the air conditioner system.
•
If the problem disappears and operation returns to normal, the CHECK display on the remote control unit will switch off, but the
self-diagnosis LED will remain illuminated until operation is resumed.
LED Symbol
Description
Off
Flashing
Illuminated
Wired remote
control unit display
Outdoor unit printed circuit board
LED
Location of problem
Check location
Abnormal
display
Detail
display
2
3
4
5
6
7
8
F15
-01
Drain level Float switch problem Drain pump and drain pipe, indoor unit
connectors
F16
-01
Louver switch problem
Louver motor, decorative panel
connection terminal, or indoor unit louver
motor connectors
F17
-02
D. C Fan Motor problem
Indoor unit D.C. Fan motor or connection
terminals
F20
-01
Indoor temperature sensor
problem
Indoor temperature sensor lead wire or
indoor unit connector
-02
Remote control thermistor
problem
Remote control thermistor
F21
-01
Pipe temp. sensor problem
(indoor unit)
Pipe temperature sensor lead wire or
indoor unit connector
F26
-01
Remote control transmission
problem
Remote control unit cable and connection
terminals
F27
-01
Indoor/outdoor unit
disconnection problem
Indoor/outdoor unit connection cable and
connection terminals, or indoor unit power
supplies (indoor side)
-05
Indoor/outdoor unit connection
error problem
Indoor/outdoor unit connection wire
(indoor side)
-01
Indoor/outdoor unit
disconnection problem
Indoor/outdoor unit connection cable and
connection terminals, or outdoor unit
power supplies (outdoor side)
-05
Indoor/outdoor unit connection
problem
Indoor/outdoor unit connection wire
(outdoor side)
F30
-01
System problem
Total capacity for the number of indoor
units is insufficient, or over. Check the
total capacity and the number of indoor
units
-02
Open phase, or reversed phase
of supply
Check the main power supply terminal
board connections, or switch over any two
of the power supply wires.
F31
-01
Suction pressure protection
Insufficient refrigerant or valve operation
(closed)
-02
High-pressure cut-off
Check the Refrigeration system
-06
4 way valve information
Check the 4 way valve or lead wire
-10
Refrigerant system problem
Valve operation (closed) or refrigerant
system
F32
-05
Compressor overcurrent
protection
Open phase or lock in compressor
-06
Compressor discharge temp.
protection
Insufficient refrigerant
F40
-21
Heat exchanger outlet
temperature sensor problem
Outdoor heat exchanger outlet
temperature sensor (COND TEMP) lead
wire, connector
-51
Compressor discharge
temperature sensor problem
Compressor discharge temperature
sensor (DIS T. TEMP) lead wire,
connector
F41
-02
High pressure switch open
circuit problem
High-pressure switch lead wire, connector
-12
Low pressure sensor problem
Low pressure sensor lead wire, connector
or valve operation (closed)
F42
-11
Current detector open circuit
Outdoor unit current detector fault or
connector compressor fault or refrigerant
system
83
Summary of Contents for CS-F14DD3E5
Page 8: ...4 DIMENSIONS 4 1 CS F14DD3E5 CS F18DD3E5 8 ...
Page 9: ...4 2 CU B14DBE5 CU B18DBE5 9 ...
Page 10: ...5 REFRIGERATION CYCLE 5 1 CS F14DD3E5 CU B14DBE5 CS F18DD3E5 CU B18DBE5 10 ...
Page 11: ...6 BLOCK DIAGRAM 6 1 CS F14DD3E5 CS F18DD3E5 6 2 CU B14DBE5 11 ...
Page 12: ...6 3 CU B18DBE5 12 ...
Page 13: ...7 WIRING DIAGRAM 7 1 CS F14DD3E5 CS F18DD3E5 13 ...
Page 14: ...7 2 CU B14DBE5 14 ...
Page 15: ...7 3 CU B18DBE5 15 ...
Page 17: ...8 2 Remote control display 17 ...
Page 18: ...8 3 Remote control panel 18 ...
Page 85: ...13 TECHNICAL DATA 13 1 Sound data 85 ...
Page 86: ...86 ...
Page 87: ...13 2 Sound measurement point 13 2 1 Indoor unit 13 2 2 Outdoor unit 87 ...
Page 89: ...HEATING 89 ...
Page 91: ...91 ...
Page 93: ...93 ...
Page 95: ...13 5 Fan performance 13 5 1 CS F14DD3E5 Fan performance test report Fan performance curve 95 ...
Page 96: ...13 5 2 CS F18DD3E5 Fan performance test report Fan performance curve 96 ...
Page 99: ...14 REPLACEMENT PARTS 14 1 Indoor unit CS F14DD3E5 CS F18DD3E5 99 ...
Page 101: ...14 2 Outdoor unit CU B14DBE5 CU B18DBE5 101 ...
Page 102: ...CU B14DBE5 CU B18DBE5 102 ...
Page 104: ...15 PRINT PATTERN 15 1 Indoor unit INDOOR UNIT PRINTED CIRCUIT BOARD MAIN 104 ...