10.4.10. Connecting power supply cables
CAUTION
•
For three phase model, never operate the unit by pressing the electromagnetic switch.
•
Never correct the phase by switching over any of the wires inside the unit.
10.4.11. Precautions with regard to test operation
•
Use only insulation tool to switch on the microswitch on the electric circuit board (do not use finger or
metalic tool).
•
Do not switch on power before all installation is completed.
•
For 3 phase power, make sure the phases are connected correctly.
(If the phases are connected incorrectly, LED indicator on the electric circuit board will start flashing.)
•
After power on, make sure the voltage is 90% ~ 110% of the rated voltage.
•
May use remote control or corresponding switches on the control panel of the outdoor unit to initiate “Test
Run”.
If “Test Run” is initiated using remote control, refer to indoor unit installation.
•
Test Run consists of
cooling and
heating modes (Single mode unit does not have heating function).
•
Press and hold SW1 more than 1 second. In DS1, under different setting condition, outdoor unit will perform
“cooling” test run or “heating” test run.
DS1
Operation mode
1
2
3
4
ON
OFF
x
x
“Cooling” test run
ON
ON
x
x
“Heating” test run
OFF
OFF
x
x
PUMP DOWN
(Must first select “cooling” mode.)
When operation mode changes, the compressor stops operation momentary.
•
Press SW1 again to cancel test run.
•
If outdoor temperature is high during “heating” test run, or low during “cooling” test run, the protection
system in the system will be activated within several minutes.
NOTE 1
These units are equipped with connection error prevention circuits. If the units do not operate, it is possible that the connection
error prevention circuits have been operated. In such cases, check that the Indoor/outdoor unit connection wire (connected to
terminals
,
and
) is connected correctly. If they are connected incorrectly, connect them correctly. Normal operation
should then commence.
NOTE 2
Do not short the remote control unit wires to each other. (The protection circuit will be activated and the units will not operate.)
Once the cause of the short is eliminated, normal operation will then be possible.
54
Summary of Contents for CS-F14DD3E5
Page 8: ...4 DIMENSIONS 4 1 CS F14DD3E5 CS F18DD3E5 8 ...
Page 9: ...4 2 CU B14DBE5 CU B18DBE5 9 ...
Page 10: ...5 REFRIGERATION CYCLE 5 1 CS F14DD3E5 CU B14DBE5 CS F18DD3E5 CU B18DBE5 10 ...
Page 11: ...6 BLOCK DIAGRAM 6 1 CS F14DD3E5 CS F18DD3E5 6 2 CU B14DBE5 11 ...
Page 12: ...6 3 CU B18DBE5 12 ...
Page 13: ...7 WIRING DIAGRAM 7 1 CS F14DD3E5 CS F18DD3E5 13 ...
Page 14: ...7 2 CU B14DBE5 14 ...
Page 15: ...7 3 CU B18DBE5 15 ...
Page 17: ...8 2 Remote control display 17 ...
Page 18: ...8 3 Remote control panel 18 ...
Page 85: ...13 TECHNICAL DATA 13 1 Sound data 85 ...
Page 86: ...86 ...
Page 87: ...13 2 Sound measurement point 13 2 1 Indoor unit 13 2 2 Outdoor unit 87 ...
Page 89: ...HEATING 89 ...
Page 91: ...91 ...
Page 93: ...93 ...
Page 95: ...13 5 Fan performance 13 5 1 CS F14DD3E5 Fan performance test report Fan performance curve 95 ...
Page 96: ...13 5 2 CS F18DD3E5 Fan performance test report Fan performance curve 96 ...
Page 99: ...14 REPLACEMENT PARTS 14 1 Indoor unit CS F14DD3E5 CS F18DD3E5 99 ...
Page 101: ...14 2 Outdoor unit CU B14DBE5 CU B18DBE5 101 ...
Page 102: ...CU B14DBE5 CU B18DBE5 102 ...
Page 104: ...15 PRINT PATTERN 15 1 Indoor unit INDOOR UNIT PRINTED CIRCUIT BOARD MAIN 104 ...