1 SERVICE INFORMATION
Notice of Address setting for NEW Duct / NEW Outdoor Unit.
The new Duct Type / New Outdoor models are possible to have address setting for twin control by automatic when main
power supply is switched on.
(Manual address setting is also possible by using Dip switch on Indoor unit P.C. board.) However,
this address setting is only
possible when made proper wiring connection and also Indoor unit should be original virgin unit
.
1.1. Example of trouble at test operation
If found out as following phenomenon at test operation on site, it may have possibility of wrong address setting.
Therefore, please ensure of the address setting.
1. LCD display of wired remote control had not illuminate although the main power supply switch is ‘on’.
2. LCD display had indicated as normal illumination when power supply switch is ‘on’, however outdoor unit cannot be operated.
(But, it is necessary to take 3 to 5 minutes for outdoor unit to start from the timing of remote control ON/OFF switch is ‘on’.)
3. P.C. board had memorized wrong setting information.
a. If main power supply is switched ‘on’ with the wrong connection.
b. When changing the connection or combination of units due to re-installation etc.
•
When changing the system from twin control to normal one to one system.
•
When making the replacement of units as master and slave etc.
1.2. Caution of test operation
Do not touch the remote control switch and do not change any wirings for one minute when the main power supply switch is ‘on’.
(Because the unit is having automatic address setting during the first one minute.)
1.3. Caution during automatic address setting
When main power supply switch is ‘on’, the P.C. board will automatically memorized the connecting system.
Consequently, when initial power supply is ‘on’, there will not be interchangeability of units even of the same type and same
capacity unit. Therefore unable to connect the unit to another system.
1.4. Caution during installation
To protect the compressor, after installation of new unit/pump down, be sure to select cooling mode first, and run the unit in this
mode for 5 minutes or more.
If the cooling operation is not executed first for five minutes or more, the heating operation cannot be executed.
1.5. Operation range
The applicable voltage range for each unit is given in “the following table”. The working voltage among the three phases must be
balanced within 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of the
rated voltage.
1.5.1. Power Supply
Model
CU-
Unit Main Power
Applicable Voltage
Phase, Volts
Hz
Maximum
Minimum
B14DBE5
B18DBE5
1~220
50
242
198
1~230
50
253
207
1~240
50
264
216
1.5.2. Indoor and Outdoor Temperature
Model 50Hz ... B14DBE5, B18DBE5
Operating
Hz
Indoor Temp. (D.B./W.B.) (°C)
Outdoor Temp. (D.B./W.B.) (°C)
Maximum
Minimum
Maximum
Minimum
Cooling
50
32/23
21/15
43/-
5/-
Heating
50
27/-
16/-
24/18
-10/-
3
Summary of Contents for CS-F14DD3E5
Page 8: ...4 DIMENSIONS 4 1 CS F14DD3E5 CS F18DD3E5 8 ...
Page 9: ...4 2 CU B14DBE5 CU B18DBE5 9 ...
Page 10: ...5 REFRIGERATION CYCLE 5 1 CS F14DD3E5 CU B14DBE5 CS F18DD3E5 CU B18DBE5 10 ...
Page 11: ...6 BLOCK DIAGRAM 6 1 CS F14DD3E5 CS F18DD3E5 6 2 CU B14DBE5 11 ...
Page 12: ...6 3 CU B18DBE5 12 ...
Page 13: ...7 WIRING DIAGRAM 7 1 CS F14DD3E5 CS F18DD3E5 13 ...
Page 14: ...7 2 CU B14DBE5 14 ...
Page 15: ...7 3 CU B18DBE5 15 ...
Page 17: ...8 2 Remote control display 17 ...
Page 18: ...8 3 Remote control panel 18 ...
Page 85: ...13 TECHNICAL DATA 13 1 Sound data 85 ...
Page 86: ...86 ...
Page 87: ...13 2 Sound measurement point 13 2 1 Indoor unit 13 2 2 Outdoor unit 87 ...
Page 89: ...HEATING 89 ...
Page 91: ...91 ...
Page 93: ...93 ...
Page 95: ...13 5 Fan performance 13 5 1 CS F14DD3E5 Fan performance test report Fan performance curve 95 ...
Page 96: ...13 5 2 CS F18DD3E5 Fan performance test report Fan performance curve 96 ...
Page 99: ...14 REPLACEMENT PARTS 14 1 Indoor unit CS F14DD3E5 CS F18DD3E5 99 ...
Page 101: ...14 2 Outdoor unit CU B14DBE5 CU B18DBE5 101 ...
Page 102: ...CU B14DBE5 CU B18DBE5 102 ...
Page 104: ...15 PRINT PATTERN 15 1 Indoor unit INDOOR UNIT PRINTED CIRCUIT BOARD MAIN 104 ...