8. Electronic scale for refrigerant charging
•
Because of the high pressure and fast vaporizing speed
of R410A, the refrigerant cannot be held in a liquid
phase inside the charging cylinder when charging is
done using the charging cylinder method, causing
bubbles to form in the measurement scale glass and
making it difficult to see the reading. (Naturally, the
conventional R22 charging cylinder cannot be used
because of the differences in the pressure resistance,
scale gradation, connecting port size, etc.)
•
The electronic scale has been strengthened by using a
structure in which the weight detector for the refrigerant
cylinder is held by four supports. It is also equipped with
two connection ports, one for R22 (7/16 UNF, 20
threads) and one for R410A (1/2 UNF, 20 threads), so
it can also be used for conventional refrigerant charging.
•
There are two types of electronic scales, one for 10-kg
cylinders and one for 20-kg cylinders. (The 10-kg
cylinder is recommended.)
Refrigerant charging is done manually by opening and
closing the valve.
9. Refrigerant cylinders
•
The R410A cylinders are labeled with the refrigerant
name, and the coating color of the cylinder protector is
pink, which is the color stipulated by ARI of the U.S.
•
Cylinders equipped with a siphon tube are available to
allow the cylinder to stand upright for liquid refrigerant
charging.
10. Charging orifice and packing for refrigerant cylinders
•
The charging orifice must match the size of the charging
hose fitting (1/2 UNF, 20 threads).
•
The packing must also be made of an HFC-resistant
material.
Fig. 7 Electronic scale for refrigerant charging
Fig. 8 Refrigerant cylinders
Fig. 9 Charging orifice and packing
11.2.3. R410A tools which are usable for R22 models
Table 9 R410A tools which are usable for R22 models
R410A tools
Usable for R22 models
(1)
Copper tube gauge for clearance adjustment
OK
(2)
Flaring tool (clutch type)
OK
(3)
Manifold gauge
NG
(4)
Charging hose
NG
(5)
Vacuum pump adaptor
OK
(6)
Electric gas leak detector for HFC refrigerant
NG
(7)
Electronic scale for refrigerant charging
OK
(8)
Refrigerant cylinder
NG
(9)
Charging orifice and packing for refrigerant cylinder
NG
67
Summary of Contents for CS-F14DD3E5
Page 8: ...4 DIMENSIONS 4 1 CS F14DD3E5 CS F18DD3E5 8 ...
Page 9: ...4 2 CU B14DBE5 CU B18DBE5 9 ...
Page 10: ...5 REFRIGERATION CYCLE 5 1 CS F14DD3E5 CU B14DBE5 CS F18DD3E5 CU B18DBE5 10 ...
Page 11: ...6 BLOCK DIAGRAM 6 1 CS F14DD3E5 CS F18DD3E5 6 2 CU B14DBE5 11 ...
Page 12: ...6 3 CU B18DBE5 12 ...
Page 13: ...7 WIRING DIAGRAM 7 1 CS F14DD3E5 CS F18DD3E5 13 ...
Page 14: ...7 2 CU B14DBE5 14 ...
Page 15: ...7 3 CU B18DBE5 15 ...
Page 17: ...8 2 Remote control display 17 ...
Page 18: ...8 3 Remote control panel 18 ...
Page 85: ...13 TECHNICAL DATA 13 1 Sound data 85 ...
Page 86: ...86 ...
Page 87: ...13 2 Sound measurement point 13 2 1 Indoor unit 13 2 2 Outdoor unit 87 ...
Page 89: ...HEATING 89 ...
Page 91: ...91 ...
Page 93: ...93 ...
Page 95: ...13 5 Fan performance 13 5 1 CS F14DD3E5 Fan performance test report Fan performance curve 95 ...
Page 96: ...13 5 2 CS F18DD3E5 Fan performance test report Fan performance curve 96 ...
Page 99: ...14 REPLACEMENT PARTS 14 1 Indoor unit CS F14DD3E5 CS F18DD3E5 99 ...
Page 101: ...14 2 Outdoor unit CU B14DBE5 CU B18DBE5 101 ...
Page 102: ...CU B14DBE5 CU B18DBE5 102 ...
Page 104: ...15 PRINT PATTERN 15 1 Indoor unit INDOOR UNIT PRINTED CIRCUIT BOARD MAIN 104 ...