Table on Shifting Frequency Zone
Temperature, X (°C)
Zone
Frequency No. Shifting:
(Intake Air - Internal Setting)
Cooling Mode / Soft Dry Mode
Heating Mode
X
-2.5
0
Shift to Freq. MIN
Shift to Freq. MAX
-2.5
X
-1.5
1
Shift to Freq. MIN
Shift to Freq. MAX
-1.5
X
-1.0
2
-2 Freq. No.
+2 Freq. No.
-1.0
X
-0.5
3
-1 Freq. No.
+1 Freq. No.
-0.5
X
+1.0
4
Same Freq. No.
Same Freq. No.
+0.5
X
+1.0
5
+1 Freq. No.
-1 Freq. No.
+1.0
X
+1.5
6
+2 Freq. No.
-2 Freq. No.
+1.5
X
+2.5
7
Shift to Freq. MAX
Shift to Freq. MIN
X
+2.5
8
Shift to Freq. MAX
Shift to Freq. MIN
Besides, the range of operation frequency will change according to the setting environment as listed below:
Condition:
Freq. no. for E9CKP
Freq. no. for E12CKP
Remarks
MIN
MAX
MIN
MAX
Cooling Mode
1
15
1
16
(a)
- if remote controller set
28°C & fan speed =
Hi
7
15
7
16
(a), (c)
- if remote controller set
28°C & fan speed =
Me-, Me, Me+, Auto
5
15
6
16
(a), (c)
- if remote controller set
28°C & fan speed =
Lo
4
15
5
16
(a), (c)
- if Powerful Mode ON
7
15
7
16
(a), (c)
Soft Dry Mode
4
7
4
8
Heating Mode
1
30
1
30
(b)
- if remote controller set
18°C & fan speed =
Hi
10
30
10
30
(b), (d)
- if remote control set
18°C & fan speed =
Me-, Me, Me+, Auto
9
30
9
30
(b), (d)
- if remote controller set
18°C & fan speed =
Lo
8
30
8
30
(b), (d)
- if Powerful Mode ON
10
30
10
30
(b), (d)
Remark:
(a)
If frequency decreases from MAX, the following frequency performed will be depending to outdoor temperature, as given in below table
(for 30 seconds only) and then continues as normal rule.
Outdoor Temperature, X (°C)
Frequency No.
X
30
13
X
30
7
(b)
(If frequency increases from Freq. No. 17, the following frequency performed is as below (for 30 seconds only) and then continue as
normal rule.
Outdoor Temperature, X (°C)
Frequency No.
X
10
10
X
X
10
13
X
4
17
(c)
When temperature different (intake - setting) < -1.0 °C or Thermo-Off activated and only valid for 120 seconds; not applicable during Soft
Dry Mode, and Anti-freezing control.
(d)
When temperature different (intake - setting) > +1.5 °C or Thermo-Off activated and only valid for 130 seconds.
19
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5