Quiet Operation
8.2.25. Quiet operation under Soft Dry operation (Dry area at Dry Mode)
Manual and Air Volume automatic (Normal operation)
8.2.26. Quiet operation (Heating)
A. Purpose
To provide quiet heating operation compare to normal operation.
B. Control condition
a. Quiet operation start condition
•
When “quiet” button at remocon is pressed.
Quiet LED illuminates.
b. Quiet operation stop condition
1. When one of the following conditions is satisfied, quiet operation stops:
a. Quiet & Powerful button is pressed.
b. Stop by OFF/ON switch.
c.
Timer “off” activates.
d. When change mode to fan only mode.
2. When quiet operation is stopped, operation is shifted to normal operation with previous setting.
Quiet LED off.
3. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
4. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode, except fan only mode.
5. During quiet operation, if timer “on” activates, quiet operation maintains.
6. After off, when on back, quiet operation is not memorised.
36
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5