8.1.4. Cooling Mode Automatic Indoor Fan Speed
The automatic fan speed for cooling operation is as shown in below patterns (a
→
b
→
c
→ →
h) with each pattern 10 seconds.
The fan speed for each level (X or Y or Z) is as below table.
Model No.
E9CKP
E12CKP
Level
X
Y
Z
X
Y
Z
Normal Operation Fan Speed No.
11
9
7
10
9
7
Powerful Mode Fan Speed No.
13
11
9
12
10
9
(a) During cooling operation, if all the following conditions occur, indoor fan speed will be shifted to Shi internally.
(i) Indoor intake air temperature
24°C.
(ii) Instructed frequency = 39 Hz (E9CKP) or 52 Hz (E12CKP).
(iii) Remote controller setting temperature = 16°C.
(iv) Remote controller setting fan speed = Hi.
(v) Outdoor air temperature
30°C.
(vi) Operation starts
30 minutes.
8.1.5. Heating Mode Indoor Fan Motor Operation (Anti Cold draft Control)
Indoor fan speed varies in accordance to indoor heat exchanger temperature, based on type of air volume and direction, as shown
below.
1. Manual Fan Speed
22
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5