14.7 Dew Prevention Control
•
To prevent dew formation at indoor unit discharge area.
•
This control starts if:
o
Cooling mode or Quiet mode is activated.
o
Remote Control setting temperature is less than 25°C.
o
Fan speed is at CLo or QLo.
o
Room temperature is constant (±1°C) for 30 minutes.
o
Compressor is continuously running.
•
Fan speed will be adjusted accordingly in this control.
o
Fan sped will be increased slowly if the unit is in quiet mode and Lo fan speed.
•
Dew prevention stop condition.
o
Remote control setting temperature is more than 25°C.
o
Fan speed is not at Lo or QLo.
o
Select Powerful operation.
Summary of Contents for CS-C12PKV
Page 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit 5 1 1 CS C9PKV CS C12PKV ...
Page 14: ...14 5 1 2 CS C18PKV CS C24PKV CS C28PKV ...
Page 15: ...15 5 2 Outdoor Unit 5 2 1 CU C9PKV 5 2 2 CU C12PKV ...
Page 16: ...16 5 2 3 CU C18PKV 5 2 4 CU C24PKV CU C28PKV ...
Page 18: ...18 7 Block Diagram 7 1 1 CS C9PKV CU C9PKV CS C12PKV CU C12PKV ...
Page 19: ...19 7 1 2 CS C18PKV CU C18PKV CS C24PKV CU C24PKV ...
Page 20: ...20 7 1 3 CS C28PKV CU C28PKV ...
Page 25: ...25 9 Electronic Circuit Diagram 9 1 CS C9PKV CU C9PKV CS C12PKV CU C12PKV ...
Page 26: ...26 9 2 CS C18PKV CU C18PKV ...
Page 27: ...27 9 3 CS C24PKV CU C24PKV ...
Page 28: ...28 9 4 CS C28PKV CU C28PKV ...
Page 31: ...31 10 1 4 Comparator Printed Circuit Board 10 1 5 Human Activity Sensor Printed Circuit Board ...
Page 45: ...45 12 2 5 Wire Stripping And Connecting Requirement ...
Page 81: ...81 Figure 3 Figure 4 17 1 1 3 To remove discharge grille Figure 5 ...
Page 83: ...83 Figure 9 Figure 10 ...
Page 87: ...87 Figure 20 Figure 21 ...
Page 88: ...88 18 Technical Data 18 1 Thermostat Characteristics Cooling Soft Dry ...
Page 114: ...114 Printed in Malaysia SZ0313 0 ...