57
•
Auto Fan Speed during Soft Dry operation.
1 Indoor fan will rotate alternately between off and Lo-.
2 At the beginning of each compressor starts operation, indoor fan will increase fan speed gradually for
deodorizing purpose.
3 When compressor turned off for 6 minutes, indoor fan will start at Lo- to circulate the air in the room. This is
to obtain the actual reading of intake air temperature.
13.4.3 Manual Fan Speed Control
•
Manual fan speed adjustment can be carried out by using the Fan Speed selection button at the remote control.
•
There are 3 types of fan speed settings: Lo, Me, Hi.
13.4.4 Indoor Fan Motor rpm Abnormal Control
•
Immediate after the fan motor is started, rpm abnormal control is performed every second.
•
During fan motor on, if fan motor feedback
≥
2550 rpm or < 50 rpm continuously for 10 seconds, the fan motor
error counter increased; fan motor is then stopped and restarted. If the fan motor error counter increased to 7,
then air conditioner will stop operation.
13.5 Outdoor Fan Speed Control
•
There is only one speed for outdoor fan motor. (Applicable for CU-C9PK, CU-C12PK and CU-C18PK)
•
There is 2 speeds for outdoor fan motor. Outdoor fan speed can be changed to Hi or Lo according to outdoor
temperature. (Applicable for CU-C24PK and CU-C28PK).
•
For Cooling and Soft Dry operation, when outdoor temperature reaches to 31°C (Hi-speed), 29°C (Lo-speed).
(Applicable for CU-C24PK and CU-C28PK).
•
When air conditioner is turned on, the compressor and the outdoor fan will operate simultaneously.
•
Likewise, both compressor and outdoor fan will stop at the same time if the unit is turned off.
13.6 Vertical Airflow Direction Control
13.6.1 Auto
Control
•
When the vertical airflow direction is set to Auto using the remote control, the louver swings up and down as
shown in the diagram.
•
When stops operation using the remote control, the discharge vent is reset and stops at the closing position.
•
During Cooling operation or Soft Dry operation, indoor fan motor may stop to rotate at certain periods. At that
condition, the louver will stop swinging.
For CS-C9PK and CS-C12PK
Upper limit for cooling mode
and soft dry mode/15°
30°
Closing
position
/ 140°
Swing up and down
Lower limit for cooling mode and
soft dry mode/45°
Horizontal
Summary of Contents for CS-C12PKV
Page 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit 5 1 1 CS C9PKV CS C12PKV ...
Page 14: ...14 5 1 2 CS C18PKV CS C24PKV CS C28PKV ...
Page 15: ...15 5 2 Outdoor Unit 5 2 1 CU C9PKV 5 2 2 CU C12PKV ...
Page 16: ...16 5 2 3 CU C18PKV 5 2 4 CU C24PKV CU C28PKV ...
Page 18: ...18 7 Block Diagram 7 1 1 CS C9PKV CU C9PKV CS C12PKV CU C12PKV ...
Page 19: ...19 7 1 2 CS C18PKV CU C18PKV CS C24PKV CU C24PKV ...
Page 20: ...20 7 1 3 CS C28PKV CU C28PKV ...
Page 25: ...25 9 Electronic Circuit Diagram 9 1 CS C9PKV CU C9PKV CS C12PKV CU C12PKV ...
Page 26: ...26 9 2 CS C18PKV CU C18PKV ...
Page 27: ...27 9 3 CS C24PKV CU C24PKV ...
Page 28: ...28 9 4 CS C28PKV CU C28PKV ...
Page 31: ...31 10 1 4 Comparator Printed Circuit Board 10 1 5 Human Activity Sensor Printed Circuit Board ...
Page 45: ...45 12 2 5 Wire Stripping And Connecting Requirement ...
Page 81: ...81 Figure 3 Figure 4 17 1 1 3 To remove discharge grille Figure 5 ...
Page 83: ...83 Figure 9 Figure 10 ...
Page 87: ...87 Figure 20 Figure 21 ...
Page 88: ...88 18 Technical Data 18 1 Thermostat Characteristics Cooling Soft Dry ...
Page 114: ...114 Printed in Malaysia SZ0313 0 ...