74
RPM shift
+0
+20
+40
+70
(ID temp) Pipe
6.0°C
4.0°C
2.0°C
5.0°C
7.0°C
3.0°C
Compressor starts for
≥
5 minutes
▲
T
≤
2.5°C for 2 minutes
Compressor
OFF
Compressor
restart
▲
T = Intake air temperature – Indoor heat exchanger temperature
14.5 Freeze Prevention Control
•
To protect indoor heat exchanger from freezing and to prevent higher volume of refrigerant in liquid form return to
compressor.
•
This control will activate when temperature of indoor heat exchanger falls below 2°C continuously for more than 4
minutes and compressor turn off.
10
Recovery
4 min
2
Indoor Heat
Exchanger
Temperature
(°C)
Compressor
OFF
•
The current fan speed will change to freeze prevention speed after 70 seconds compressor on. The fan speed
will be increased according to the indoor pipe temperature as below figure: (Applicable for C9PKV and C12PKV
ONLY)
•
Compressor will restart again when the indoor heat exchanger temperature rises to 10°C (Recovery).
•
Restart control (Time Delay Safety Control) will be applied in this control if the recovery time is too short.
14.6 Compressor Reverse Rotation Protection Control
•
If the compressor is operating continuously for 5 minutes or longer and the temperature difference between
intake air and indoor heat exchanger is 2.5°C or less for continuously 2 minutes, compressor will stop and restart
automatically.
•
Time Delay Safety Control is activated before the compressor restart.
•
This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
•
If this condition happens continuously for 5 times within 50 minutes, unit will turn OFF with TIMER LED blinks.
•
The 5 Times counter can be reset when either one of the following condition happen:
o
Unit is OFF by remote control or AUTO OFF/ON button.
o
Indoor intake temperature – Indoor piping temperature > 5°C for one minute or more.
o
Operation mode change.
•
The unit could be ON by pressing OFF/ON button at remote control but the TIMER LED will continue blinking.
•
TIMER LED blinking will be reset if:
o
Indoor intake temperature – Indoor piping temperature > 5°C for one minute or more.
o
Power supply reset.
Summary of Contents for CS-C12PKV
Page 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit 5 1 1 CS C9PKV CS C12PKV ...
Page 14: ...14 5 1 2 CS C18PKV CS C24PKV CS C28PKV ...
Page 15: ...15 5 2 Outdoor Unit 5 2 1 CU C9PKV 5 2 2 CU C12PKV ...
Page 16: ...16 5 2 3 CU C18PKV 5 2 4 CU C24PKV CU C28PKV ...
Page 18: ...18 7 Block Diagram 7 1 1 CS C9PKV CU C9PKV CS C12PKV CU C12PKV ...
Page 19: ...19 7 1 2 CS C18PKV CU C18PKV CS C24PKV CU C24PKV ...
Page 20: ...20 7 1 3 CS C28PKV CU C28PKV ...
Page 25: ...25 9 Electronic Circuit Diagram 9 1 CS C9PKV CU C9PKV CS C12PKV CU C12PKV ...
Page 26: ...26 9 2 CS C18PKV CU C18PKV ...
Page 27: ...27 9 3 CS C24PKV CU C24PKV ...
Page 28: ...28 9 4 CS C28PKV CU C28PKV ...
Page 31: ...31 10 1 4 Comparator Printed Circuit Board 10 1 5 Human Activity Sensor Printed Circuit Board ...
Page 45: ...45 12 2 5 Wire Stripping And Connecting Requirement ...
Page 81: ...81 Figure 3 Figure 4 17 1 1 3 To remove discharge grille Figure 5 ...
Page 83: ...83 Figure 9 Figure 10 ...
Page 87: ...87 Figure 20 Figure 21 ...
Page 88: ...88 18 Technical Data 18 1 Thermostat Characteristics Cooling Soft Dry ...
Page 114: ...114 Printed in Malaysia SZ0313 0 ...