61
o
RPM control during Hi & Me cool
•
Auto Fan Speed
•
Quiet operation stops when:
o
Quiet button is pressed again.
o
Stopped by OFF/ON operation button.
o
Timer OFF activates.
o
Operation mode button is changed.
13.10
Timer Control
13.10.1 ON Timer
•
When the ON Timer is set by using the remote control, the unit will start to operate slightly before the set time, so
that the room will reach nearly to the set temperature by the set time.
•
For Cooling and Soft Dry operation, the operation will start 15 minutes before the set time.
•
For Automatic operation, the indoor fan will operate at SLo speed for 20 seconds, 15 minutes before the set time
to detect the intake air temperature to determine the operation mode. The power LED will blink.
13.10.2 OFF Timer
•
When the OFF Timer is set using the remote control, the unit will stop operate according to the desired setting.
Notes:
1 By pressing ON/OFF operation button, the ON Timer or OFF Timer will not be cancel.
2 To cancel the previous timer setting, press CANCEL button.
3 To activate the previous timer setting, press SET button.
4 If main power supply is switched off, the Timer setting will be cancel.
13.11 Random Auto Restart Control
•
If there is a power failure during operation, the air conditioner will automatically restart after 3 to 4 minutes when
the power is resumed.
•
It will start with previous operation mode and airflow direction.
•
If there are more than one air conditioner unit in operation and power failure occur, restart time for each unit to
operate will be decided randomly using 4 parameters:- intake air temperature, setting temperature, fan speed
and air swing louver position.
•
This Random Auto Restart Control is not available when Timer is set.
•
This control can be omitted by open the circuit of JX02 at indoor unit printed circuit board.
13.12 Remote Control Signal Receiving Sound
•
Short beep sound will be heard when turn ON the air conditioner or enabling other operations.
•
Long beep sound will be heard when turn OFF the air conditioner or disabling other operations.
Summary of Contents for CS-C12PKV
Page 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit 5 1 1 CS C9PKV CS C12PKV ...
Page 14: ...14 5 1 2 CS C18PKV CS C24PKV CS C28PKV ...
Page 15: ...15 5 2 Outdoor Unit 5 2 1 CU C9PKV 5 2 2 CU C12PKV ...
Page 16: ...16 5 2 3 CU C18PKV 5 2 4 CU C24PKV CU C28PKV ...
Page 18: ...18 7 Block Diagram 7 1 1 CS C9PKV CU C9PKV CS C12PKV CU C12PKV ...
Page 19: ...19 7 1 2 CS C18PKV CU C18PKV CS C24PKV CU C24PKV ...
Page 20: ...20 7 1 3 CS C28PKV CU C28PKV ...
Page 25: ...25 9 Electronic Circuit Diagram 9 1 CS C9PKV CU C9PKV CS C12PKV CU C12PKV ...
Page 26: ...26 9 2 CS C18PKV CU C18PKV ...
Page 27: ...27 9 3 CS C24PKV CU C24PKV ...
Page 28: ...28 9 4 CS C28PKV CU C28PKV ...
Page 31: ...31 10 1 4 Comparator Printed Circuit Board 10 1 5 Human Activity Sensor Printed Circuit Board ...
Page 45: ...45 12 2 5 Wire Stripping And Connecting Requirement ...
Page 81: ...81 Figure 3 Figure 4 17 1 1 3 To remove discharge grille Figure 5 ...
Page 83: ...83 Figure 9 Figure 10 ...
Page 87: ...87 Figure 20 Figure 21 ...
Page 88: ...88 18 Technical Data 18 1 Thermostat Characteristics Cooling Soft Dry ...
Page 114: ...114 Printed in Malaysia SZ0313 0 ...