43
11.3.5 Connect the cable to the Outdoor Unit
a) INDOOR POWER SUPPLY MODEL (1.0 ~
2.5HP)
1 Remove the control board cover from the
unit by loosening the screw.
2
Connection cable
between indoor unit and
outdoor unit shall be approved
polychloroprene sheathed 3 x 1.5 mm
2
(1.0 ~
1.5HP) or 3 x 2.5 mm
2
(2.0 ~ 2.5HP) flexible
cord, type designation 245 IEC 57 or heavier
cord. Do not use joint connection cable.
Replace the wire if the existing wire (from
concealed wiring, or otherwise) is too short.
3 Secure the cable onto the control board with
the holder.
4 Attach the control board cover back to the
original position with the screw.
5 For wire stripping and connection requirement,
refer to instruction
g
of the indoor unit.
WARNING
This equipment must be properly earthed.
Earth wire shall be Yellow/Green (Y/G) in colour
and longer than the other AC wires for safety
reason.
b) OUTDOOR POWER SUPPLY MODEL (3.0HP)
1 Remove the control board cover from the unit by loosening the screw.
2 Cable connection to the power supply through Isolating Devices (Disconnecting means).
o
Connect the approved polychloroprene sheathed
power supply cord
3 x 4.0 mm
2
(3.0HP) type
designation 245 IEC 57 or heavier cord to the terminal board, and connect the other end of the cord to
Isolating Devices (Disconnecting means).
o
Do not use joint power supply cord. Replace the wire if the existing wire (from concealed wiring, or
otherwise) is too short.
o
In unavoidable case, joining of power supply cord between isolating devices and terminal board of air
conditioner shall be done by using approved socket and plug rated 25A (3.0HP). Wiring work to both
socket and plug must follow to national wiring standard.
3
Connection cable
between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 x
1.5 mm
2
flexible cord, type designation 245 IEC 57 or heavier cord. Do not use joint connection cable.
Replace the wire if the existing wire (from concealed wiring, or otherwise) is too short.
4 Connect the power supply cord and connection cable between indoor unit and outdoor unit according to the
diagram below.
5 Secure the power supply cord and connection cable onto the control board with the holder.
6 Attach the control board cover back to the original position with screw.
Summary of Contents for CS-C12MKV
Page 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit 5 1 1 CS C9MKV CS C12MKV ...
Page 14: ...14 5 1 2 CS C18MKV CS C24MKV CS C28MKV ...
Page 15: ...15 5 2 Outdoor Unit 5 2 1 CU C9MKV 5 2 2 CU C12MKV ...
Page 16: ...16 5 2 3 CU C18MKV CU C24MKV CU C28MKV ...
Page 17: ...17 6 Refrigeration Cycle Diagram ...
Page 18: ...18 7 Block Diagram 7 1 1 CS C9MKV CU C9MKV CS C12MKV CU C12MKV ...
Page 19: ...19 7 1 2 CS C18MKV CU C18MKV CS C24MKV CU C24MKV ...
Page 20: ...20 7 1 3 CS C28MKV CU C28MKV ...
Page 26: ...26 9 Electronic Circuit Diagram 9 1 CS C9MKV CU C9MKV ...
Page 27: ...27 9 2 CS C12MKV CU C12MKV ...
Page 28: ...28 9 3 CS C18MKV CU C18MKV ...
Page 29: ...29 9 4 CS C24MKV CU C24MKV ...
Page 30: ...30 9 5 CS C28MKV CU C28MKV ...
Page 32: ...32 10 1 1 2 CS C18MKV CS C24MKV CS C28MKV ...
Page 34: ...34 10 1 6 Human Activity Sensor Printed Circuit Board ...
Page 77: ...77 Figure 3 Figure 4 16 1 1 3 To remove discharge grille Figure 5 ...
Page 79: ...79 Figure 9 Figure 10 ...
Page 81: ...81 16 2 1 3 To remove power electronic controller Figure 13 Figure 14 Figure1 5 ...
Page 83: ...83 Figure 19 Figure 20 Figure 21 ...
Page 85: ...85 16 3 1 3 To remove power electronic controller Figure 24 Figure 8 Figure 9 ...
Page 87: ...87 Figure 30 Figure 31 Figure 32 ...
Page 88: ...88 17 Technical Data 17 1 Thermostat Characteristics Cooling Soft Dry ...