14. Servicing
Mode
14.1 Auto OFF/ON Button
Auto OFF/ON
Button Pressed
Auto OFF/ON
Button Pressed
Auto OFF/ON
Button Pressed
5 sec
5 sec
Auto Operation
Test Run Operation
(Forced Cooling Operation)
Stop
Various Setting Mode
Stop
“Beep”
2 x “Beep”
1 AUTO OPERATION MODE
The Auto Operation will be activated immediately once the Auto OFF/ON button is pressed. This operation
can be used to operate air conditioner with limited function if remote control is misplaced or malfunction.
2 TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE)
The Test Run Operation will be activated if the Auto OFF/ON button is pressed continuously for more than 5
seconds. A “beep” sound will be heard at the fifth seconds, in order to identify the starting of this operation.
3 VARIOUS SETTING MODE
The Various Setting Mode will be activated if (within 20 seconds of Test Run Operation) the Auto OFF/ON
button is pressed for more than 5 seconds. 2 “beep” sounds will be heard to identify the starting of this
operation.
Under Various Setting Mode, user could perform the following operation:
i. Press Auto OFF/ON button to toggle remote control receiving sound.
- Short “beep”: Turn ON remote control receiving sound.
- Long “beep”: Turn OFF remote control receiving sound.
After Auto OFF/ON button is pressed, the 20 seconds counter for Remote Control Receiving Sound OFF/ON
Mode is restarted.
ii. Remote Control Number Switch.
- There are 4 types of remote control transmission code could be selected and stored in EEPROM of
indoor unit. The indoor unit will only operate when received signal with same transmission code from
remote control. This could prevent signal interference when there are 2 or more indoor units installed
nearby together.
- To change remote control transmission code, short or open jumpers at the remote control printed circuit
board.
Remote Control Printed Circuit Board
Jumper A (J1)
Jumper B (D2)
Remote Control No.
Short Open A
(Default)
Open Open
B
Short Short
C
Open Short
D
- During Various Setting Mode, press any button at remote control to transmit and store the desired
transmission code to the EEPROM.
- After signal is received, the Various Setting Mode is cancelled and return to normal operation.
- If there is no code is transmitted of Auto OFF/ON button is not pressed within 20 seconds, the
Various Setting Mode will be cancelled.
Summary of Contents for CS-C12MKV
Page 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit 5 1 1 CS C9MKV CS C12MKV ...
Page 14: ...14 5 1 2 CS C18MKV CS C24MKV CS C28MKV ...
Page 15: ...15 5 2 Outdoor Unit 5 2 1 CU C9MKV 5 2 2 CU C12MKV ...
Page 16: ...16 5 2 3 CU C18MKV CU C24MKV CU C28MKV ...
Page 17: ...17 6 Refrigeration Cycle Diagram ...
Page 18: ...18 7 Block Diagram 7 1 1 CS C9MKV CU C9MKV CS C12MKV CU C12MKV ...
Page 19: ...19 7 1 2 CS C18MKV CU C18MKV CS C24MKV CU C24MKV ...
Page 20: ...20 7 1 3 CS C28MKV CU C28MKV ...
Page 26: ...26 9 Electronic Circuit Diagram 9 1 CS C9MKV CU C9MKV ...
Page 27: ...27 9 2 CS C12MKV CU C12MKV ...
Page 28: ...28 9 3 CS C18MKV CU C18MKV ...
Page 29: ...29 9 4 CS C24MKV CU C24MKV ...
Page 30: ...30 9 5 CS C28MKV CU C28MKV ...
Page 32: ...32 10 1 1 2 CS C18MKV CS C24MKV CS C28MKV ...
Page 34: ...34 10 1 6 Human Activity Sensor Printed Circuit Board ...
Page 77: ...77 Figure 3 Figure 4 16 1 1 3 To remove discharge grille Figure 5 ...
Page 79: ...79 Figure 9 Figure 10 ...
Page 81: ...81 16 2 1 3 To remove power electronic controller Figure 13 Figure 14 Figure1 5 ...
Page 83: ...83 Figure 19 Figure 20 Figure 21 ...
Page 85: ...85 16 3 1 3 To remove power electronic controller Figure 24 Figure 8 Figure 9 ...
Page 87: ...87 Figure 30 Figure 31 Figure 32 ...
Page 88: ...88 17 Technical Data 17 1 Thermostat Characteristics Cooling Soft Dry ...