69
13. Protection
Control
13.1 Restart Control (Time Delay Safety Control)
When the thermo-off temperature (temperature which compressor stops to operate) is reach during:-
o
Cooling operation – the compressor stops for 3 minutes (minimum) before resume operation.
o
Soft Dry operation – the compressor stops for 6 minutes (minimum) before resume operation.
If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the
moment operation stop, although the unit is turn on again within the period.
This phenomenon is to balance the pressure inside the refrigerant cycle.
13.2 7 Minutes Time Save Control
The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls
between the compressor ON temperature (A) and compressor OFF temperature (B) during the period.
This phenomenon is to reduce the built up humidity inside a room.
13.3 60 Seconds Forced Operation
Once the air conditioner is turned on, the compressor will not stop within 60 seconds in a normal operation
although the intake air temperature has reached the thermo-off temperature. However, forced stop by pressing
the OFF/ON operation button at the remote control is permitted.
The reason for the compressor to force operate at the minimum 60 seconds is to allow the refrigerant oil run in a
full cycle and return back to the outdoor unit.
13.4 Starting Current Control
When the compressor, outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor
will start to operate at 1.6 seconds later.
The reason of the difference is to reduce the starting current flow.
Summary of Contents for CS-C12MKV
Page 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit 5 1 1 CS C9MKV CS C12MKV ...
Page 14: ...14 5 1 2 CS C18MKV CS C24MKV CS C28MKV ...
Page 15: ...15 5 2 Outdoor Unit 5 2 1 CU C9MKV 5 2 2 CU C12MKV ...
Page 16: ...16 5 2 3 CU C18MKV CU C24MKV CU C28MKV ...
Page 17: ...17 6 Refrigeration Cycle Diagram ...
Page 18: ...18 7 Block Diagram 7 1 1 CS C9MKV CU C9MKV CS C12MKV CU C12MKV ...
Page 19: ...19 7 1 2 CS C18MKV CU C18MKV CS C24MKV CU C24MKV ...
Page 20: ...20 7 1 3 CS C28MKV CU C28MKV ...
Page 26: ...26 9 Electronic Circuit Diagram 9 1 CS C9MKV CU C9MKV ...
Page 27: ...27 9 2 CS C12MKV CU C12MKV ...
Page 28: ...28 9 3 CS C18MKV CU C18MKV ...
Page 29: ...29 9 4 CS C24MKV CU C24MKV ...
Page 30: ...30 9 5 CS C28MKV CU C28MKV ...
Page 32: ...32 10 1 1 2 CS C18MKV CS C24MKV CS C28MKV ...
Page 34: ...34 10 1 6 Human Activity Sensor Printed Circuit Board ...
Page 77: ...77 Figure 3 Figure 4 16 1 1 3 To remove discharge grille Figure 5 ...
Page 79: ...79 Figure 9 Figure 10 ...
Page 81: ...81 16 2 1 3 To remove power electronic controller Figure 13 Figure 14 Figure1 5 ...
Page 83: ...83 Figure 19 Figure 20 Figure 21 ...
Page 85: ...85 16 3 1 3 To remove power electronic controller Figure 24 Figure 8 Figure 9 ...
Page 87: ...87 Figure 30 Figure 31 Figure 32 ...
Page 88: ...88 17 Technical Data 17 1 Thermostat Characteristics Cooling Soft Dry ...