27
11.4.5.
Freeze Prevention Control
• To protect indoor heat exchanger from freezing and to prevent higher volume of refrigerant in liquid form return to compressor.
• This control will activate when the temperature of indoor heat exchanger falls below 2
°
C continuously for more than 4 minutes.
• The current fan speed will change to freeze prevention speed after 70 seconds compressor on. When indoor pipe temperature
reaches certain temperature for 5 sec. the speed will be increased as in below figure.
• Compressor will turn off when indoor temperature falls below 2
°
C for more than 4 minutes. It will restart again when indoor heat
exchanger temperature rises to 10
°
C.
• Restart control (Time Delay Safety Control) will be applied in this control.
11.4.6.
Compressor Reverse Rotation Protection Control
• If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and indoor
heat exchanger is 2.5
°
C or less for continuous 2 minutes, compressor will stop and restart automatically.
• Time Delay Safety Control is activated before the compressor restart.
•
This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
Summary of Contents for CS-C12EKF
Page 9: ...9 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS C12EKF ...
Page 10: ...10 5 2 Outdoor Unit 5 2 1 CU C12EKF ...
Page 11: ...11 6 Refrigeration Cycle Diagram ...
Page 12: ...12 7 Block Diagram ...
Page 14: ...14 9 Printed Circuit Board 9 1 Indoor Unit TOP VIEW ...
Page 15: ...15 BOTTOM VIEW ...
Page 16: ...16 9 2 Indicator TOP VIEW BOTTOM VIEW ...
Page 42: ...42 15 Technical Data 15 1 Thermostat Characteristics Cooling Soft Dry ...
Page 43: ...43 15 2 Operation Characteristics 15 2 1 CS C12EKF CU C12EKF ...
Page 44: ...44 ...
Page 46: ...46 ...