28
11.4.7.
Dew Prevention control
• To prevent dew formation at indoor unit discharge area.
• This control will be activated if:-
- Cooling mode or Quiet mode.
- Remote Control setting temperature is less than 25
°
C.
- Fan speed is at Low or QLo.
- Room temperature is constant (±1
°
C) for 30 minutes.
- Compressor is continuously running.
• Fan speed and angle of horizontal louver (vertical airflow angle) will be adjusted accordingly in this control.
- Fan speed will be increased slowly if the unit is in quiet mode but no change in normal cooling mode.
- The angle of horizontal louver will be changed as below figure.
Note:
A = Normal operation angle of rotation
B = Dew prevention angle of rotation
Horizontal Louver Angle
During dew prevention, the horizontal louver angle in Auto-control are as below figure.
During dew prevention, the horizontal louver angle in Manual control are as below figure.
Operation mode
Airflow direction auto-control
Airflow direction manual control
Cooling, Soft Dry
A
12
°
~ 32
°
12
°
, 15
°
, 20
°
, 26
°
, 32
°
B
20
°
~ 30
°
22
°
, 24
°
, 26
°
, 28
°
, 30
°
Summary of Contents for CS-C12EKF
Page 9: ...9 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS C12EKF ...
Page 10: ...10 5 2 Outdoor Unit 5 2 1 CU C12EKF ...
Page 11: ...11 6 Refrigeration Cycle Diagram ...
Page 12: ...12 7 Block Diagram ...
Page 14: ...14 9 Printed Circuit Board 9 1 Indoor Unit TOP VIEW ...
Page 15: ...15 BOTTOM VIEW ...
Page 16: ...16 9 2 Indicator TOP VIEW BOTTOM VIEW ...
Page 42: ...42 15 Technical Data 15 1 Thermostat Characteristics Cooling Soft Dry ...
Page 43: ...43 15 2 Operation Characteristics 15 2 1 CS C12EKF CU C12EKF ...
Page 44: ...44 ...
Page 46: ...46 ...