13.24 Overload Protection Control
•
Outdoor
Fan
Control
o
If the temperature of the Outdoor Heat Exchanger less than -3°C, Outdoor Fan is ON. The Outdoor Fan stop,
when Outdoor Heat Exchanger temperature is Tb or more according to Outdoor Air Temperature region as
table below:
The Outdoor Fan restarts when the indoor heat exchanger temperature falls to 49°C.
Outdoor Air
Temperature
< 10°C
10°C ~ < 15°C 5°C ~ < 20°C 20°C ~ < 25°C
25°C
Tb
5°C
3°C
1.5°C
0.5°C
0.5°C
Outdoor Fan
OFF
During starting of Heating mode and after deice, Outdoor Fan ON for 90 sec. (Hi).
•
Compressor High Pressure Control
o
If the indoor heat exchanger becomes 68°C or more, the compressor will stop and restart automatically.
o
Time Delay Safety Control is activated before the compressor restart.
13.25 4-Way Valve Control
•
4-way valve always on during Heating operation. (except deicing operation)
•
When the unit is switched off by remote control during Heating operation, the 4-way valve stay at Heating
position for 5 minutes.
•
This is to prevent the refrigerant flow process sound for being occur.
13.26 Hot Start Control
•
Hot Start Control is to prevent cool air discharge into the room when heating operation start.
•
When Heating operation starts, Indoor fan will not start until the indoor heat exchanger reaches 30°C as diagram
shown.
•
Hot start is completed when indoor heat exchanger rises to 42°C or operation over 4 minutes.
Summary of Contents for CS-A12KKD-2
Page 3: ...3 18 Exploded View and Replacement Parts List 125 18 1 Indoor Unit 125 18 2 Outdoor Unit 131 ...
Page 16: ...16 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 17: ...17 5 Dimensions 5 1 Indoor Unit 5 1 1 CS A9KKD 2 CS A12KKD 2 ...
Page 18: ...18 5 1 2 CS A18KKD 2 CS A24KKD 2 CS A28KKD 2 ...
Page 19: ...19 5 2 Outdoor Unit 5 2 1 CU A9KKD 2 5 2 2 CU A12KKD 2 ...
Page 20: ...20 5 2 3 CU A18KKD 2 CU A24KKD 2 CU A28KKD 2 ...
Page 21: ...21 6 Refrigeration Cycle Diagram 6 1 CS A9KKD 2 CU A9KKD 2 CS A12KKD 2 CU A12KKD 2 ...
Page 22: ...22 6 2 CS A18KKD 2 CU A18KKD 2 CS A24KKD 2 CU A24KKD 2 CS A28KKD 2 CU A28KKD 2 ...
Page 23: ...23 7 Block Diagram 7 1 CS A9KKD 2 CU A9KKD 2 ...
Page 24: ...24 7 2 CS A12KKD 2 CU A12KKD 2 ...
Page 25: ...25 7 3 CS A18KKD 2 CU A18KKD 2 CS A24KKD 2 CU A24KKD 2 ...
Page 26: ...26 7 4 CS A28KKD 2 CU A28KKD 2 ...
Page 31: ...31 9 Electronic Circuit Diagram 9 1 CS A9KKD 2 CU A9KKD 2 ...
Page 32: ...32 9 2 CS A12KKD 2 CU A12KKD 2 ...
Page 33: ...33 9 3 CS A18KKD 2 CU A18KKD 2 CS A24KKD 2 CU A24KKD 2 ...
Page 34: ...34 9 4 CS A28KKD 2 CU A28KKD 2 ...
Page 36: ...36 10 1 1 2 CS A28KKD 2 ...
Page 39: ...39 10 1 7 Eco Patrol Printed Circuit Board ...
Page 86: ...86 Normal Deice Time Diagram Overload Deice Time Diagram ...
Page 91: ...91 a Normal Deice Time Diagram b Overload Deice Time Diagram ...
Page 97: ...97 Figure 3 Figure 4 Figure 5 16 1 1 3 To remove discharge grille Figure 6 ...
Page 99: ...99 Figure 10 Figure 11 ...
Page 101: ...101 16 2 1 3 To remove power electronic controller Figure 14 Figure 15 Figure 16 Figure 17 ...
Page 103: ...103 Figure 21 Figure 22 Figure 23 ...
Page 104: ...104 17 Technical Data 17 1 Thermostat Characteristics ...