Evacuation of the Equipment
1
Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way
valve.
o
Be sure to connect the end of the charging hose with the push pin to the service port.
2
Connect the center hose of the charging set to a vacuum pump.
3
Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0
cmHg (0 MPa) to -76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
4
Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the
gauge does not move after approximately five minutes.
Note: BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERENT GAS LEAKAGE.
5
Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6
Tighten the service port caps of the 3-way valve at a torque of 18 N•m with a torque wrench.
7
Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN”
using a hexagonal wrench (4 mm).
8
Mount valve caps onto the 2-way valve and the 3-way valve.
o
Be sure to check for gas leakage.
CAUTION
•
If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-01 MPa), in the step
e
above take the following measure:
-
If the leak stops when the piping connections are tightened further, continue working from step
e
.
-
If the leak does not stop when the connections are retightened, repair location of leak.
-
Do not release refrigerant during piping work for installation and reinstallation.
-
Take care of the liquid refrigerant, it may cause frostbite.
Summary of Contents for CS-A12KKD-2
Page 3: ...3 18 Exploded View and Replacement Parts List 125 18 1 Indoor Unit 125 18 2 Outdoor Unit 131 ...
Page 16: ...16 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 17: ...17 5 Dimensions 5 1 Indoor Unit 5 1 1 CS A9KKD 2 CS A12KKD 2 ...
Page 18: ...18 5 1 2 CS A18KKD 2 CS A24KKD 2 CS A28KKD 2 ...
Page 19: ...19 5 2 Outdoor Unit 5 2 1 CU A9KKD 2 5 2 2 CU A12KKD 2 ...
Page 20: ...20 5 2 3 CU A18KKD 2 CU A24KKD 2 CU A28KKD 2 ...
Page 21: ...21 6 Refrigeration Cycle Diagram 6 1 CS A9KKD 2 CU A9KKD 2 CS A12KKD 2 CU A12KKD 2 ...
Page 22: ...22 6 2 CS A18KKD 2 CU A18KKD 2 CS A24KKD 2 CU A24KKD 2 CS A28KKD 2 CU A28KKD 2 ...
Page 23: ...23 7 Block Diagram 7 1 CS A9KKD 2 CU A9KKD 2 ...
Page 24: ...24 7 2 CS A12KKD 2 CU A12KKD 2 ...
Page 25: ...25 7 3 CS A18KKD 2 CU A18KKD 2 CS A24KKD 2 CU A24KKD 2 ...
Page 26: ...26 7 4 CS A28KKD 2 CU A28KKD 2 ...
Page 31: ...31 9 Electronic Circuit Diagram 9 1 CS A9KKD 2 CU A9KKD 2 ...
Page 32: ...32 9 2 CS A12KKD 2 CU A12KKD 2 ...
Page 33: ...33 9 3 CS A18KKD 2 CU A18KKD 2 CS A24KKD 2 CU A24KKD 2 ...
Page 34: ...34 9 4 CS A28KKD 2 CU A28KKD 2 ...
Page 36: ...36 10 1 1 2 CS A28KKD 2 ...
Page 39: ...39 10 1 7 Eco Patrol Printed Circuit Board ...
Page 86: ...86 Normal Deice Time Diagram Overload Deice Time Diagram ...
Page 91: ...91 a Normal Deice Time Diagram b Overload Deice Time Diagram ...
Page 97: ...97 Figure 3 Figure 4 Figure 5 16 1 1 3 To remove discharge grille Figure 6 ...
Page 99: ...99 Figure 10 Figure 11 ...
Page 101: ...101 16 2 1 3 To remove power electronic controller Figure 14 Figure 15 Figure 16 Figure 17 ...
Page 103: ...103 Figure 21 Figure 22 Figure 23 ...
Page 104: ...104 17 Technical Data 17 1 Thermostat Characteristics ...