Aquarea air/water heat pump – Installation manual for monobloc and split systems C, D and E series 05 / 2014
Electrical installation
Mains connections
Monobloc systems
➤
Cut into the cable gland in a cross shape using a knife .
➤
Route the cables through the enclosed cable gland on the right side
of the housing to prevent the cables being damaged by sharp edges .
➤
Connect the mains connection cable as shown in the diagrams .
Ensure that the earthing cable is slightly longer than the other cables .
➤
Use the strain reliefs to secure the mains connection cables .
➤
Connect the other end of the mains connection cable to the fuses .
➤
Open the monobloc unit as described in section 5 .1 .
➤
Use cables compliant with 60245 IEC 57 or thicker for the mains
connections .
1
Mains connections
2
Cable ties
3
Cable gland
2
3
1
Laying the cables inside the device