REFERENCE
4.3 List of Pulse_4Axes Parameters
15.3.8 Movement Does Not Stop at Home Position (after decelerating for
home return)
■
Situation
There is a possibility that the PG_Home has not been executed correctly.
■
Solution 1
Forcibly turn the home input sensor ON and OFF from an external source, and check to see if
the home input display LED "Z" on the pulse output unit lights.
■
Solution 2
Check to see if the input valid logic for the home input is normally either ON or OFF.
■
Solution 3
● Check the parameter for home return.
● As a default, the home input is set to "NC contact". When the home input is not connected,
the unit processes as the home input is invalid.
REFERENCE
4.3 List of Pulse_4Axes Parameters
15.3 What to Do If an Error Occurs
15-8
WUME-GM1PG-01
Summary of Contents for AGM1PG04L
Page 2: ... MEMO 2 WUME GM1PG 01 ...
Page 14: ... MEMO 1 4 WUME GM1PG 01 ...
Page 22: ... MEMO 2 8 WUME GM1PG 01 ...
Page 42: ... MEMO 3 20 WUME GM1PG 01 ...
Page 52: ...4 5 Increment and Absolute 4 10 WUME GM1PG 01 ...
Page 70: ...AccDec 10000 END_CASE 6 1 Sample Program 6 6 WUME GM1PG 01 ...
Page 82: ... MEMO 7 10 WUME GM1PG 01 ...
Page 90: ... MEMO 8 8 WUME GM1PG 01 ...
Page 94: ...AccDec 10000 END_CASE 9 1 Sample Program 9 4 WUME GM1PG 01 ...
Page 116: ... MEMO 10 20 WUME GM1PG 01 ...
Page 124: ... MEMO 11 8 WUME GM1PG 01 ...
Page 142: ... MEMO 14 4 WUME GM1PG 01 ...
Page 158: ...16 3 Dimensions 16 3 1 Pulse Output Unit Unit mm 16 3 Dimensions 16 8 WUME GM1PG 01 ...
Page 162: ... MEMO App 4 WUME GM1PG 01 ...
Page 164: ... MEMO WUME GM1PG 01 ...
Page 165: ... MEMO WUME GM1PG 01 ...
Page 166: ...Panasonic Corporation 2021 August 2021 WUME GM1PG 01 ...