![Panasonic AFP7CPS31 User Manual Download Page 34](http://html.mh-extra.com/html/panasonic/afp7cps31/afp7cps31_user-manual_262250034.webp)
4-2
Installation
and Wiring
4.1 Installation
4.1.1 Installation Environment and Space
Installation environment
Operating environment (Use the unit within the range of the general specifications when
installing)
Ambient temperatures: 0 to +55
C
Ambient humidity: 10 to 95%RH (at 25
C, no-condensing)
Pollution degree 2
Usable altitude: 2,000m above sea level or lower
Equipment class: Class 1
Overvoltage category: II or lower
Installation location: Inside the control panel
Do not use the unit in the following environments.
- Direct sunlight
- Sudden temperature changes causing condensation
- Inflammable or corrosive gas
- Excessive airborne dust, metal particles or saline matter
- Benzine, paint thinner, alcohol or other organic solvents or strong alkaline solutions such as
ammonia or caustic soda
- Direct vibration, shock or direct drop of water.
- Influence from power transmission lines, high voltage equipment, power cables, power
equipment, radio transmitters, or any other equipment that would generate high switching
surges (100 mm or more)
Clearance
In order to secure clearance for ventilation, ensure that the top and the bottom of the unit are
at least 50 mm away from other devices, wiring ducts, etc.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for AFP7CPS31
Page 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 9: ...1 Overview Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 47: ...5 Operation Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 62: ...5 16 Operation Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 77: ...8 Specifications Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...