1.3
Restrictions
1-7
1.3 Restrictions
Connecting to External Devices
LAN ports 1 and 2 have the same IP address and MAC address.
•
Do not connect the cables from the two LAN ports to the same switching HUB.
•
When performing dasiy chain connection, do not connect devices in a ring shape.
HUB
Number of connections
For the FP0H, the total number of connections of Ethernet communication and EtherNet/IP
communication should be 9 or less. For the details of the setting of the number of connection,
refer to “3.2.1 Ethernet Settings”.
(The no. of user connections of Ethernet communication) + (EtherNet/IP communication)
≤
9
connections
Restrictions by FP0H specifications
Item
Specifications
RPI
1 to 10000 ms (In 0.5 ms unit)
Cyclic communication allowable
communication band
5000 pps (Packet size: 2 to 510 bytes)
2500 pps (Packet size: 511 to 1450 bytes)
Usable devices
WX, WY, WR, WL, DT, LD
Device specification of each tag/instance
Max. 8 devices
Summary of Contents for AFP0HC32ET
Page 1: ......
Page 11: ...1 FP0H EtherNet IP Function ...
Page 18: ...FP0H EtherNet IP Function 1 8 ...
Page 19: ...2 Cyclic Communication ...
Page 27: ...3 Setting Procedure ...
Page 50: ...Setting Procedure 3 24 ...
Page 51: ...4 Tool Operation ...
Page 69: ...5 Startup and Operation ...
Page 78: ...Startup and Operation 5 10 ...
Page 79: ...6 Instruction References ...
Page 88: ...Instruction References 6 10 ...
Page 89: ...7 Reference Information ...
Page 97: ...8 Appendix ...
Page 100: ......
Page 101: ......
Page 102: ......