4.8 System’s plan No. 8
Functioning
:
The pump1 is on at the threshold
A01.
If the fireplace works
(threshold
A01),
The 3 outputs valve is commutated to the accumulation until the value of the
parameter
A04 (probe2). The parameter A05 (probe2) is the value of the new
commutation in phase of decrease of the temperature probe2.
The 3 outputs valve with spring return is normally to the distribution system.
Make sure the accumulation has a security dissipation.
Used IN/OUT
SERIGRAPHY
CONNECTORS
System’s symbol
Probe1
Probe1
15 - 16
S1
Pompa1
Pompa
13 - 14
P1
Probe2
Probe2
17 - 18
S2
3 outputs valve
AUX
6 - 7
V1
INSTALLER’S MENU PARAMETERS’ SET (Par. 3.5)
Parameter
Description
U.
Min Default
Max
C- -
System’s configuration
n
C01
C08
C08
A10
Alarm thermostat
°C
60
85
90
P01
Probe’s type: ‘
0’ =10K blue; ‘1’ 100K grey
n
0
0
1
P02
Activation output’s AUX (6-7) protection functions
n
0
0
1
Parameters USER’S MENU (Par. 5.0)
Parameter
Description
U.
Min Default
Max
A01
Starting threshold pump1
°C
20
50
70
A04
Extinguishing threshold 3 outputs valve
°C
50
60
80
A05
Re-starting threshold 3 output valve
°C
50
55
80
I01
Thermostat hysteresis parameter
A01
°K
0
2
5
I04
Thermostat hysteresis parameter
A04
°K
0
2
5
I05
Thermostat hysteresis parameter
A05
°K
0
2
5
N
L-
O
N
1 2 3 4 5 6 7 8 9 10 11 12 13 14
20 19 18 17 16 15
N
L-
O
N
SCHEMA N. 8 TERMOPALEX WITH HEATING SYSTEM AND BOILER FOR THE PRODUCTION
OF HOT SANITARY WATER
C1:controller
P1
S1
HSo
HSi
S2
BOILER
CONFIGURATION
C08
D
distribution
system
Hot
sanitary
water
Cold
sanitary
water
V1: 3 outputs valve