Pag.: 60/60
Cod. 004770370
TC120
ANTIFREEZING Function:
PUMP
If the temperature read by the probe1, also in case of device OFF, goes under the anti freezing Thermostat
A09 [4°C]
:
The output PUMP is activated
The led
L1 is activated, and the display shows
ICE
AUX: if activated the installer’s parameter P02 = 1
If the temperature read by the Probe2 goes under the anti freezing Thermostat
A09 [4°C]
:
The output AUX (6-7) is activated
The led
L3 is activated and the display shows
ICE
ALARM Function:
If the temperature read by the Probe goes over the value of the Alarm thermostat
A10
The display shows the signal
SIC
The acoustic signal is activated
SILENCE function: the acoustic signal could be deactivated for 5 minutes pushing a button; then if the alarm
is still on, the signal is activated again.
TEST PUMP
Function
Pushing the button
The output
PUMP is activated for a time as the pushing of the button;
The led
L1 is activated and the display shows
tSt
.
TEST AUX
Function
Through the long pushing of the button
The output
AUX (6-7) is activated for a time as the pushing of the button;
The led
L3 is activated and the display shows
tSt
.
6.3 SIGNAL OF FAILURES OR ALARMS
The control signals failures of the probes through blinking messages:
Lo : indicates out of scale to the low
(temperature under-10 °C)
Probe cut or not connected
Hi : indicates out of scale to the high
(temperature over110 °C)
Probe in short circuit
In case of probes 100K (old model) on controller TC120 and P01=0 appears the message
Lo.
In case of probes 10K (new model) on controller TC200 appears the message
Hi or temperature increased of 50 °C more
than in reality.
Power: 230 Vac
±
10% 50 Hz; protection fuse T 1,6A
Dimension: In box controller: 140 x 80 x 50 [mm]
Supply: 2 VA
Rules:
EN 60730-1 50081-1 EN 60730-1 A1
50081-2
Table
5 – Technical characteristics
For a continuous development its own products, the builder reserves itself the right to bring performances changes and technical data without warning. The consumer is
guaranteed against the defects of conformity of the product for 24 months from the date of sale according to the European Directive 1999/44/F. The seller has got the
complete text of the guarantee. The firm doesn't respond for due damages to wrong wirings or improper use of the device.
7.0
Controller TC200 SUBSTITUTION
In case of changing of the only controller (fig.4) NOT of the sensors,
•
Modify the installer’s parameter
P01
(Par.
3.5):
change the value from ’
0’ to
’1’
.
In this way the new controller could manage the old probes.