Pag.: 56/60
Cod. 004770370
TC120
4.6 System’s plan No. 6
Functioning
:
The pump1 starts at the threshold
A01.
The 3 outputs valve is commutated to the boiler
at the threshold
A04.
The 3 outputs valve with spring return is normally to the fireplace.
Make sure the boiler has a security dissipation.
Used IN/OUT
SERIGRAPHY
CONNECTORS
System’s symbol
Probe1
Probe1
15 - 16
S1
Pompa1
Pump
13 - 14
P1
Probe2
Probe2
17 - 18
S2
3 outputs valve
AUX
6 - 7
V1
INSTALLER’S MENU PARAMETERS’ SET (Par. 3.5)
Parameter
Description
U.
Min Default
Max
C- -
System’s configuration
n
C01
C06
C08
A10
Alarm thermostat
°C
60
85
90
P01
Probe’s type: ‘
0’ =10K blue; ‘1’ 100K grey
n
0
0
1
P02
Activation output’s AUX (6-7) protection functions
n
0
0
1
Parameters USER’S MENU (Par. 5.0)
Parameter
Description
U.
Min Default
Max
A01
Starting threshold pump1
°C
20
50
70
A03
Differential thermostat Probe1 - Probe2
°K
0
4
20
I01
Thermostat hysteresis parameter
A01
°K
0
2
5
I03
Thermostat hysteresis parameter
A03
°K
0
2
5
PLAN No. 6
TERMOPALEX WITH PARALLEL
HEATING SYSTEM
AND INERTIAL ACCUMULATION SYSTEM
GAS BOILER
S1
C1: controller
P1
S2
HSo
B
HSi
BOILER
SOLAR
CONFIGURATION
C06
V1
D
distribution
system
SANITARY
HOT
WATER
Sanitary
cold
water
Gas
mural
thermic
group
3 exits
valve
N
L-
O
N
1 2 3 4 5 6 7 8 9 10 11 12 13 14
20 19 18 17 16 15
N
L-
O
N