background image

The achieved competence should be documented by a certificate.

Training

The training should include the substance of the following:
Information about the explosion potential of flammable refrigerants to show that 
flammables may be dangerous when handled without care.
Information about potential ignition sources, especially those that are not 
obvious, such as lighters, light switches, vacuum cleaners, electric heaters.
Information about the different safety concepts:
Unventilated – (see Clause GG.2) Safety of the appliance does not depend on 
ventilation of the housing. Switching off the appliance or opening of the housing 
has no significant effect on the safety. Nevertheless, it is possible that leaking 
refrigerant may accumulate inside the enclosure and flammable atmosphere 
will be released when the enclosure is opened. 
Ventilated enclosure – (see Clause GG.4) Safety of the appliance depends on 
ventilation of the housing. Switching off the appliance or opening of the enclo-
sure has a significant effect on the safety. Care should be taken to ensure a 
sufficient ventilation before.
Ventilated room – (see Clause GG.5) Safety of the appliance depends on the 
ventilation of the room. Switching off the appliance or opening of the housing 
has no significant effect on the safety. The ventilation of the room shall not be 
switched off during repair procedures.
Information about the concept of sealed components and sealed enclosures
according to IEC 60079-15:2010.
Information about the correct working procedures:
a) Commissioning
• Ensure that the floor area is sufficient for the refrigerant charge or that the 
ventilation duct is assembled in a correct manner.
• Connect the pipes and carry out a leak test before charging with refrigerant.
• Check safety equipment before putting into service.
b) Maintenance
• Portable equipment shall be repaired outside or in a workshop specially

12

equipped for servicing units with flammable refrigerants.
• Ensure sufficient ventilation at the repair place.
• Be aware that malfunction of the equipment may be caused by refrigerant loss 
and a refrigerant leak is possible.
• Discharge capacitors in a way that won’t cause any spark. The standard 
procedure to short circuit the capacitor terminals usually creates sparks.
• Reassemble sealed enclosures accurately. If seals are worn, replace them.
• Check safety equipment before putting into service.
c) Repair
• Portable equipment shall be repaired outside or in a workshop specially 
equipped for servicing units with flammable refrigerants.
• Ensure sufficient ventilation at the repair place.
• Be aware that malfunction of the equipment may be caused by refrigerant loss 
and a refrigerant leak is possible.
• Discharge capacitors in a way that won’t cause any spark.
• When brazing is required, the following procedures shall be carried out in the 
right order:
– Remove the refrigerant. If the recovery is not required by national regulations, 
drain the refrigerant to the outside. Take care that the drained refrigerant will 
not cause any danger. In doubt, one person should guard the outlet. Take 
special care that drained refrigerant will not float back into the building.
– Evacuate the refrigerant circuit.
– Purge the refrigerant circuit with nitrogen for 5 min.
– Evacuate again.
– Remove parts to be replaced by cutting, not by flame.
– Purge the braze point with nitrogen during the brazing procedure.
– Carry out a leak test before charging with refrigerant.
• Reassemble sealed enclosures accurately. If seals are worn, replace them.
• Check safety equipment before putting into service.
d) Decommissioning
• If the safety is affected when the equipment is putted out of service, the 
refrigerant charge shall be removed before decommissioning.

13

Summary of Contents for PA010996

Page 1: ...let Room temperature is higher than the setting temperature Electric heating mode Room temperature is lower than the setting temperature Cooling mode The doors or windows are not closed There are heat...

Page 2: ...f the refrigerant circuit If the appliance is installed operated or stored in a nonventilated area the room must be designed to prevent to the accumulation of refrigerant leaks resulting in a risk of...

Page 3: ...y cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard 12 This appliance can be used by children aged from 8 years and ab...

Page 4: ...e avoid ed The area around the workspace shall be sectioned off Ensure that the conditions within the area have been made safe by control of flammable material 1 4 Checking for presence of refrigerant...

Page 5: ...stem that there is continuity of earth bonding 2 REPAIRS TO SEALED COMPONENTS 2 1 During repairs to sealed components all electrical supplies shall be discon nected from the equipment being worked upo...

Page 6: ...igerant charge shall be recovered into the correct recovery cylin ders The system shall be flushed with OFN to render the unit safe This process may need to be repeated several times Compressed air or...

Page 7: ...harge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the recovery of refrigerant Cylin ders shall be co...

Page 8: ...safety equipment before putting into service b Maintenance Portable equipment shall be repaired outside or in a workshop specially 12 equipped for servicing units with flammable refrigerants Ensure su...

Page 9: ...cause any spark Remove the refrigerant If the recovery is not required by national regulations drain the refrigerant to the outside Take care that the drained refrigerant will not cause any danger In...

Page 10: ...dehumidification and sleep mode the wind speed cannot be adjust ed The wind speed will be locked in low wind SLEEP 1 When in cooling mode when press the sleep button to enter sleep mode an hour later...

Page 11: ...ress on off to start up and then press on off to shut down WIND Press the swing wind button to start the swing wind function Press the swing button again and the left and right swing function will be...

Page 12: ...ctions of all machines can be realized through WIFI mobile APP Note optional function is to supply consumers according to the need to choose the specification shows the full functionality Temperature...

Page 13: ...ric safety require ments When using functions on cooling and dehumidifying keep an interval of at least 3 minutes between each POWER Power supply meets the requirements The socket is for AC use Do not...

Page 14: ...8 Fig 9 25 Maintenance Explanations Declaration 1 Before cleaning be sure to disconnect the unit from any electric supply outlet 2 Do not use gasoline or other chemicals to clean the unit 3 Do not was...

Reviews: