background image

a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure ensure that :mechanical handling equipment 
is available, if required, for handling refrigerant cylinders; all personal protective 
equipment is available and being used correctly; the recovery process is 
supervised at all times by a competent person; recovery  equipment  and  
cylinders conform to the appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be 
removed from various parts of the system.
f) Make sure that cylinder is situated on the scales before recovery takes place.
g) Start the recovery machine and operate in accordance with manufacturer's 
instructions.
h) Do not overfill cylinders. (No more than 80 % volume liquid charge).
i) Do not exceed the maximum working pressure of the cylinder,even temporari-
ly.
j) When the cylinders have been filled correctly and the process completed, 
make sure that the cylinders and the equipment are removed from site promptly 
and all isolation valves on the equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigeration system
unless it has been cleaned and checked.

10 LABELLING

Equipment shall be labelled stating that it has been de-commissioned and 
emptied of refrigerant.The label shall be dated and signed.
Ensure that there are labels on the equipment stating the equipment contains 
flammable refrigerant.

11 RECOVERY

When removing refrigerant from a system, either for servicing or decommission-
ing, it is recommended good practice that all refrigerants are removed safely. 
When transferring refrigerant into cylinders, ensure that only

10

appropriate refrigerant recovery cylinders are employed. Ensure that the 
correct number of cylinders for holding the total system charge are available.All 
cylinders to be used are designated for the recovered refrigerant and labelled 
for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylin-
ders shall be complete with pressure relief valve and associated shut-off valves 
in good working order. Empty recovery cylinders are evacuated and, if possible, 
cooled before recovery occurs.
The recovery equipment shall be in good working order with a set of instruc-
tions concerning the equipment that is at hand and shall be suitable for the 
recovery of flammable refrigerants.In addition,a set of calibrated weighing 
scales shall be available and in good working order. Hoses shall be complete 
with leak-free disconnect couplings and in good condition. Before using the 
recovery machine, check that it is in satisfactory working order, has been 
properly maintained and that any associated electrical components are sealed 
to prevent ignition in the event of a refrigerant release. Consult manufacturer if 
in doubt. 
The recovered refrigerant shall be returned to the refrigerant supplier in the 
correct recovery cylinder,and the relevant Waste Transfer Note arranged. Do 
not mix refrigerants in recovery units and especially not in cylinders. 
If compressors or compressor oils are to be removed, ensure that they have 
been evacuated to an acceptable level to make certain that flammable refriger-
ant does not remain within the lubricant. The evacuation process shall be 
carried out prior to returning the compressor to the suppliers. Only electric 
heating to the compressor body shall be employed to accelerate this 
process.When oil is drained from a system,it shall be carried out safely.

Competence of service personnel

General

Special training additional to usual refrigerating equipment repair procedures is 
required when equipment with flammable refrigerants is affected.
In many countries, this training is carried out by national training organisations 
that are accredited to teach the relevant national competency standards that 
may be set in legislation.

11

Summary of Contents for PA010996

Page 1: ...let Room temperature is higher than the setting temperature Electric heating mode Room temperature is lower than the setting temperature Cooling mode The doors or windows are not closed There are heat...

Page 2: ...f the refrigerant circuit If the appliance is installed operated or stored in a nonventilated area the room must be designed to prevent to the accumulation of refrigerant leaks resulting in a risk of...

Page 3: ...y cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard 12 This appliance can be used by children aged from 8 years and ab...

Page 4: ...e avoid ed The area around the workspace shall be sectioned off Ensure that the conditions within the area have been made safe by control of flammable material 1 4 Checking for presence of refrigerant...

Page 5: ...stem that there is continuity of earth bonding 2 REPAIRS TO SEALED COMPONENTS 2 1 During repairs to sealed components all electrical supplies shall be discon nected from the equipment being worked upo...

Page 6: ...igerant charge shall be recovered into the correct recovery cylin ders The system shall be flushed with OFN to render the unit safe This process may need to be repeated several times Compressed air or...

Page 7: ...harge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the recovery of refrigerant Cylin ders shall be co...

Page 8: ...safety equipment before putting into service b Maintenance Portable equipment shall be repaired outside or in a workshop specially 12 equipped for servicing units with flammable refrigerants Ensure su...

Page 9: ...cause any spark Remove the refrigerant If the recovery is not required by national regulations drain the refrigerant to the outside Take care that the drained refrigerant will not cause any danger In...

Page 10: ...dehumidification and sleep mode the wind speed cannot be adjust ed The wind speed will be locked in low wind SLEEP 1 When in cooling mode when press the sleep button to enter sleep mode an hour later...

Page 11: ...ress on off to start up and then press on off to shut down WIND Press the swing wind button to start the swing wind function Press the swing button again and the left and right swing function will be...

Page 12: ...ctions of all machines can be realized through WIFI mobile APP Note optional function is to supply consumers according to the need to choose the specification shows the full functionality Temperature...

Page 13: ...ric safety require ments When using functions on cooling and dehumidifying keep an interval of at least 3 minutes between each POWER Power supply meets the requirements The socket is for AC use Do not...

Page 14: ...8 Fig 9 25 Maintenance Explanations Declaration 1 Before cleaning be sure to disconnect the unit from any electric supply outlet 2 Do not use gasoline or other chemicals to clean the unit 3 Do not was...

Reviews: