Operation procedures
Version 1.3, 2021-12-14
55
1
2
3
4
5
5.1.4
How to switch the IntrCooll® off
There are several situations from which the IntrCooll® can be switched off. To
switch the IntrCooll® off:
-
If the unit is on 'stand by', the main switch (1) can be switched off
immediately.
-
If the IntrCooll® is in active cooling mode and a thermostat has been fitted:
a) Set the on / off switch on the thermostat to off.
b) Switch off the main switch (1) on the IntrCooll®.
Warning
Do NOT turn off the IntrCooll® by interrupting the main voltage. The unit must
be able to fully run the automatic drying cycle.
Note
Legionella prevention. After switching off the system, the content of the water
tank is saved for a maximum of 60 minutes, after which it is automatically
emptied.
Note
If the IntrCooll did not receive a cooling request for an hour, the drying cycle
automatically starts. When the IntrCooll® cools the whole day, the drying cycle
starts at night (time set).
Note
The Oxyvap® pads need to dry to minimize bacterial growth. The silver ions in
the coating on the slats can kill the bacteria present.
Note
Only when the IntrCooll® is switched off for a shorter period of time (max
4 hours), can the drying cycle be skipped.
5.1.5
Switch off for longer periods
5.1.5.1
Take the IntrCooll® out of service
When the IntrCooll® is out of use for a longer period, obey the precautions below:
-
Make sure that no water remains in the sump, heat exchangers and Oxyvap®
media.
Normally the sump drains automatically when the IntrCooll® is de-energized.
-
Disconnect the mains water connection and bleed the water supply line.