background image

 

Open  casing  by  pushing  back  the  snap  hooks  at  the  lower  side 
with  a  3.5  mm  screwdriver.  Now  fix  casing  with  the  help  of  the 
enclosed  screws.  Finally  carry  out  wiring  according  to  the  wiring 
diagram (illustr. 6.1) and close casing again. 

 

The installation location of the room thermostat must comply with 
the following conditions:  

  The  room  thermostat  must  not  be  exposed  to  a  direct  heat 

source (e.g. sunlight) or cold source. 

  A good air circulation must be guaranteed.  

  The room thermostat must be easily accessible. 

 

Operation 

The  display  shows  the  current  room  temperature  (RT)  at  the 
installation location. The current time and day of the week as well 
as  the  set  operating  mode  and  the  setting  of  the  fan  are  also 
displayed. 

 

7.1 

Switching the thermostat off/on 

The thermostat and display are switched off by pressing the key 

. The thermostat is switched on again by pressing the key 

 

once more. 

 

7.2 

Frost protection mode 

To  activate  the  frost  protection,  switch  the  thermostat  off  by 

pressing the key 

Now  keep  the  key 

  pressed  for  about  3  seconds.  “00“ 

(inactivated)  appears  on  the  display.  Now  chose  “01“  (activated) 
by pressing the key 

If  the  room  temperature  drops  below  5°C,  the  thermostat  is 
switched  on  automatically.  The  room  temperature  is  now 
increased  to  7°C.  Having  reached  this  value,  the  thermostat  is 
switched off again automatically. 
As supplied, the frost protection is switched off. 

 

7.3 

Temperature calibration 

Temperature calibration must only be carried out  if the indicated 
temperature is not correct. 

Switch  off  the  room  thermostat  by  using  the  key 

.  Now  press 

the keys 

 and 

 simultaneously for about 3 seconds. The room 

temperature  which  visualises  on  the  display  is  adapted  with  the 
help of the keys 

 or 

The calibration settings are stored by pressing the key 

 

7.4 

Operating functions 

The operating function can be chosen with the key 

 heating, 

 cooling, 

 ventilation 

 
 
 

7.5 

Fan setting 

The fan speed can be set with the key 

 slow,   medium,   fast,  

 automatic (only for heating and cooling) 

 

7.6 

Normal operating mode 

RT

: Thermostat in operating mode; the display indicates “RT“ and 

the current room temperature. 

SET

:  By  pressing  the  key 

  or 

  once,  the  display  indicates 

“SET“ and the set nominal temperature. The nominal temperature 
can be increased or reduced with the help of the keys 

 and 

This  temperature  modification  is  only  active  until  the  next 
programmed temperature. 

 

7.7 

Setting the time and the day of the week 

Press the key 

. Now set the hours with the help of the keys 

 

and 

 and press 

 to set the minutes. Now press 

 again and 

set the day of the week. 

 

7.8 

Setting of the weekly programme 

Setting of the nominal temperature for the days of the week (Mo-
Fr)  and  the  weekend  (Sa-Su)  are  autonomous.  4  time  intervals 
per day can be set. 
Press the key 

 for about 3 seconds. The display now indicates 

1 (SET 1) and “Mo. Tu. We. Th. Fr.“. The first time interval for the 
days of the week can now be set. 
Use  the  keys 

  and 

  to  set  the  required  start-up  time  and 

confirm  it  by  pressing  the  key 

.  Set  the  required  temperature 

using  the  keys 

  and 

  and  confirm  it  by  pressing  the  key 

Repeat this procedure for the time intervals 2-4 of the days of the 
week. 
Now the settings for the weekend (the display shows “Su.    Sa.“) 
can be carried out the same way. 

 

Example 
Room  temperature  for  the  days  of  the  week  shall  be  set  as 
follows. 
Temperature sequence: 

Required setting: 

05:30 – 08:00 h  22°C  

Number 1: 05:30; 22°C 

08:00 – 14:00 h  18°C  

Number 2: 08:00; 18°C 

14:00 – 23:00 h  23°C  

Number 3: 14:00; 23°C 

23:00 – 05:30 h  19°C  

Number 4: 23:00; 19°C 

 

Maintenance 

The  room  thermostat  must  only  be  cleaned  with  mild  detergent. 
Detergents  must  not  penetrate  the  room  thermostat,  they  must 
not be sprayed onto the thermostat but onto a cleaning cloth. 
 

General  terms  and  conditions  of  sale  and 
delivery 

Oventrops general terms and conditions of sale and delivery valid 
at the time of supply are applicable. 

 

Summary of Contents for 1152451

Page 1: ...d durch Symbole gekennzeichnet Diese Hinweise sind zu befolgen um Unf lle Sachsch den und St rungen zu vermeiden GEFAHR weist auf eine unmittelbar gef hr liche Situation hin die zum Tod oder zu schwer...

Page 2: ...Schaltungen Schutzart IP 30 4 2 Abmessungen Anschlussma e Abb 4 1 Abmessungen 5 Aufbau und Funktion Abb 5 1 Displayanzeigen und Druckknopffunktionen 5 1 Funktionsbeschreibung Der Digitale Raumthermost...

Page 3: ...7 5 Ventilatoreinstellungen Die Geschwindigkeit des Ventilators kann mit der Taste eingestellt werden langsam mittel schnell Automatik nur f r Heizen und K hlen 7 6 Normaler Betriebsmodus RT Thermost...

Page 4: ...installation and operating instructions are copyrighted 1 4 Symbol explanation Safety guidelines are displayed by symbols These guidelines are to be observed to prevent accidents damage to property an...

Page 5: ...4 2 Dimensions Connection dimensions Illustr 4 1 Dimensions 5 Construction and function Illustr 5 1 Display and functions of press buttons 5 1 Functional description The digital room thermostat is use...

Page 6: ...n be chosen with the key heating cooling ventilation 7 5 Fan setting The fan speed can be set with the key slow medium fast automatic only for heating and cooling 7 6 Normal operating mode RT Thermost...

Page 7: ...ignes doivent tre respect es pour viter des accidents des d g ts mat riels et des dysfonctionnements DANGER signifie une situation imm diate dangereuse qui peut mener la mort et provoquer des blessure...

Page 8: ...de raccordement Fig 4 1 Encombrements 5 Construction et fonctionnement Fig 5 1 Affichages digitaux et fonctions des touches 5 1 Description du fonctionnement Le thermostat d ambiance digital s utilis...

Page 9: ...du ventilateur La vitesse du ventilateur peut tre r gl e l aide de la touche lente moyenne rapide automatique seulement pour chauffer et rafra chir 7 6 Mode de service normal RT Thermostat en mode de...

Reviews: