D-160TS-7-E
34
16. LOOPTEST (OUTPUT SIMULATION)
Looptest generates pulse output as simulation in order to confirm the connection between the flowmeter
and an external instrument. Looptest can be executed from sub-menu [Fix.PL] under Setting Mode
[mAint].
Output frequency and output pulse count can be set at any value with in the ranges of 1.0 to 2000.0Hz,
and 0 to 99999999, respectively.
ENT
SEL
ENT Hold
SEL Hold
・Operation procedure
Pulse output
on hold
Hold ENT to set pulse
frequency.
Hold ENT to set output
pulse count.
Output start
If Count=0, output continues
until ENT is pressed.
If Count≠0
Automatic
Fig. 16.1