Operation
26
900-0020-01-00 Rev A
Multiple-Inverter Installations (Stacking)
Multiple inverters in a single system can support larger loads than a single inverter can handle.
Installing inverters in this configuration is called “stacking”. Stacking inverters does not refer to
physically placing one on top of another. It refers to how they are wired within the system and then
programmed to coordinate activity. Stacking allows all units to work together as one system.
The Radian inverter can be stacked in parallel to increase capacity. Up to ten units can be stacked to
operate in a single system. Each inverter is programmed to operate at certain times.
Stacking requires an OutBack HUB product, as well as a MATE3 system display (sold separately). A
system of four or fewer units may use the HUB4. Systems of up to ten units require the HUB10. All
interconnections are made using CAT5 non-crossover cable. (See the
Radian SeriesInverter/Charger
Installation Manual
for more stacking instructions.)
Each inverter needs to be assigned a status — “master” or “slave”. The master is the primary and most
heavily used unit. Slave inverters provide assistance when the loads are more than the master can
handle alone. Programming involves using the MATE3 to assign a status and stacking value to the
inverter on each port. See the MATE3 and HUB manuals for programming instructions.
Figure 6 OutBack HUB4 and MATE3
IMPORTANT:
The master inverter must always be connected to port 1 on the HUB. Connecting
it elsewhere, or connecting a slave to port 1, will result in backfeed or output
voltage errors which will shut the system down immediately.
Installing multiple inverters without stacking them (or stacking them incorrectly)
will result in similar errors and shutdown.
Although stacking allows greater capacity, the loads, wiring, and overcurrent
devices must still be sized appropriately. Additional terminations and bus bars
may be required. Overloading may cause circuit breakers to open or the inverters
to shut down.
Additional Ports
Port 1
MATE Port
HUB4
MATE3
Summary of Contents for Radian GS8048
Page 1: ...Radian Series Inverter Charger GS8048 Operator s Manual...
Page 40: ...Troubleshooting 38 900 0020 01 00 Rev A NOTES...
Page 46: ...Troubleshooting 44 900 0020 01 00 Rev A NOTES...
Page 56: ...Warranty 54 900 0020 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK...
Page 59: ...900 0020 01 00 Rev A 57 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 60: ...North America 5917 195th St NE 7 Arlington WA 98223 USA 1 360 435 6030 900 0020 01 00 Rev A...