Specifications
900-0020-01-00 Rev A
47
The acceptance ranges are selected using the system display. In the MATE3, the options are
IEEE
and
user.
The
IEEE
option allows a range of 108 – 132 Vac at 59.3 – 60.5 Hz
The
user
option does not have a fixed voltage setting. It follows the upper and lower limit settings in the
Grid AC Input Mode and Limits menu. The default is a range of 108 – 132 Vac.
Reconnection delay is 6 seconds. Sell delay is 5 minutes. These settings are not adjustable.
Firmware Revision
This manual applies to Radian series inverter/chargers with a firmware version of 001.000.xxx
or higher.
Default Settings and Ranges
Table 11
GS8048 Inverter Settings
Field Item
Default
Minimum
Maximum
INVERTER
Hot Key
Inverter Mode
Off On
,
Off
, or
Search
CHARGER
Hot Key
Charger Control
On On
or
Off
AC Input
Hot Key
AC Input Mode
Use Drop
or
Use
Sensitivity
(see page 16 for increments)
10 0 250
Pulse Length
8 AC cycles
4 AC cycles
20 AC cycles
Search
Pulse Spacing
60 AC cycles
4 AC cycles
120 AC cycles
Input Priority
Grid
Grid
or
Gen
Grid Input AC Limit
50 Aac
5 Aac
55 Aac
Gen Input AC Limit
50 Aac
5 Aac
55 Aac
AC Input and
Current Limit
Charger AC Limit
30 Aac
0 Aac
30 Aac
Input Mode
Grid Tied
Generator, Support, Grid Tied, UPS, Backup,
Mini Grid
Voltage Limit Lower
108 Vac
70 Vac
110 Vac
(
Voltage Limit)
Upper
132 Vac
125 Vac
140 Vac
Transfer Delay
6 AC cycles
0 AC cycles
240 AC cycles
Grid AC Input
Mode and Limits
Connect Delay
0.2 minutes
0.2 minutes
15 minutes
Input Mode
Generator
Generator, Support, Grid Tied, UPS, Backup,
Mini Grid
Voltage Limit Lower
108 Vac
70 Vac
110 Vac
(Voltage Limit)
Upper
140 Vac
125 Vac
140 Vac
Transfer Delay
6 AC cycles
0 AC cycles
240 AC cycles
Gen AC Input
Mode and Limits
Connect Delay
0.5 minutes
0.2 minutes
15 minutes
AC Output
Output Voltage
240 Vac
220 Vac
260 Vac
Cut-Out Voltage
42 Vdc
36 Vdc
48 Vdc
Low Battery
Cut-In Voltage
50 Vdc
40 Vdc
56 Vdc
Absorb Voltage
57.6 Vdc
52 Vdc
64 Vdc
(Absorb)
Time
1.0 hours
0.0 hours
24.0 hours
Float Voltage
54.4 Vdc
48 Vdc
60 Vdc
(Float)
Time
1.0 hours
0.0 hours
24.0 hours
Battery Charger
Re-Float Voltage
50 Vdc
48 Vdc
52 Vdc
Equalize Voltage
58.4 Vdc
56 Vdc
68 Vdc
Battery Equalize
(Equalize)
Time
1.0 hours
0.0 hours
24.0 hours
Summary of Contents for Radian GS8048
Page 1: ...Radian Series Inverter Charger GS8048 Operator s Manual...
Page 40: ...Troubleshooting 38 900 0020 01 00 Rev A NOTES...
Page 46: ...Troubleshooting 44 900 0020 01 00 Rev A NOTES...
Page 56: ...Warranty 54 900 0020 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK...
Page 59: ...900 0020 01 00 Rev A 57 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 60: ...North America 5917 195th St NE 7 Arlington WA 98223 USA 1 360 435 6030 900 0020 01 00 Rev A...