5.4 Connect the SE 200 to the LogoSens 2 via the 4 … 20 mA
interface
䡵
Connect the SE 200 as shown in Figure 7 to the LogoSens 2 Station
M
anager
using the connecting cable.
Please follow the LogoSens 2 Station
M
anager operating instructions as well.
Configuring the LogoSens 2 for SE 200 with the 4 … 20 mA
interface
䡵
Create a LogoSens 2 channel using the
I 4-20 mA function block
(
Analog Sensors tab).
䡵
Apply the following settings:
䊳
Terminal block
A … R
Connection terminal of the SE 200
䊳
Sensor lag time (s)
0
no lag time necessary
䊳
Error code if range overflow
If necessary: Recording error codes
when measuring ranges are exceeded
䊳
Auxiliary sensor supply via relay
Not necessary in connection
contact at terminal block
䡵
Insert a
2-point scale function block and make the appropriate settings
(e. g. for an SE 200 with a 10 m measuring range and level measurement:
Point 1: 4
→
0 ; Point 2: 20
→
10).
䡵
In the
Channel function block, adjust to the required units and number of digits
after the decimal point.
Fig. 8: Adjusting the LogoSens 2
I 4-20mA
function block operating parameters.
4 … 20
m
A
i
n
put
Power
supply
se
n
sor
Screwed ter
m
i
n
al strip T
Screwed ter
m
i
n
al strip A … R
Co
nn
ecti
n
g li
n
e SE 200
brow
n
+Vcc
white GND
+V
Bat
= typ. +12 V
0 V
+V
Bat
4
3
1
2
4
3
1
2
Resistor
100 Oh
m
LogoSe
n
s 2
Fig. 7: Connecting the SE 200 to the
LogoSens 2 Station
M
anager using
a 4 … 20 mA Interface.
Use the 100 Ohm OTT resistor
(order number: 55.550.126.4.2)!
10