PRODUCT SETTINGS AND CONFIGURATION
OI-6000K-X-X-X-NXP-X OPS_GUIDE_REV 1.0
30
3.10
MODBUS BAUD SETTING
The baud rate is the speed of data transmitted within the Modbus system, measured in bits per second (bps).
For successful communication, the baud rate setting of the OI-6000K
MUST
match the baud rate setting on
the attached Otis Monitor, or other Modbus device.
All Otis devices have factory default Modbus baud settings of 9600 bps.
The RS-485 Modbus communication
parameters used in all Otis devices are
8 data bits, no parity bit, and 1 stop bit (8-N-1)
these parameters are
fixed and cannot be changed.
Some devices come with different Modbus baud rates. Check with your
system administrator to determine if a different Modbus baud setting is needed for your system.
The pre-set Modbus baud setting available for the OI-6000K are the following:
◼
110 bps
◼
300 bps
◼
1200 bps
◼
2400 bps
◼
4800 bps
◼
9600 bps
◼
19200 bps
1.
Use the
ADD
and
SUB
buttons to scroll through the available Modbus baud options.
2.
Press the
MENU
button to select the desired setting and to advance to the 4-20 mA offset settings
screen.