INSTALLATION AND STARTUP
OI-6000K-X-X-X-NXP-X OPS_GUIDE_REV 1.0
8
2.3.1
OPENING THE ENCLOSURE
To prepare the OI-6000K for installation, you must first open the device, exposing the control
board and its components for wiring.
1.
Open the enclosure lid by unlatching the right-side enclosure latches.
2.
Using your thumb and forefinger, loosen the front panel thumbscrews that secure the
faceplate and electronics assembly to the enclosure.
3.
Open the faceplate to expose the internals of the electronics which allows access to the
wiring terminals.
NOTICE
Disconnecting the sensor connector plug from the digital sensor board will allow for the
faceplate and electronics assembly to swing open further. Disconnecting the digital sensor
board may provide ease in accessing the control board terminals for wiring. If this step is
performed, it is essential that all connections are rejoined before securing the faceplate and
electronics assembly back to the enclosure.
2.3.2
CONNECTING POWER
The AC model OI-6000K comes with a standard power cord that is plugged into a regular wall
outlet, you may skip the below DC wiring instructions and advance to the 4-20 wiring if that
functionality is desired. To provide DC power to the OI-6000K, you will need to connect the power
cable from the sensor terminal block on an Otis monitor, or alternate user supplied power source,
to the OI-6000K power terminal block located on the backplane of the enclosure. An electrician
will need to install the proper cord grip for the cabling being used. Refer to the following
instructions for how to wire your device:
On the GEN II Model OI-6000K Detector:
1.
Feed the power wires through the electrician installed cord grip and into the enclosure.
2.
Locate the power terminal block on the backplane and complete the following:
a.
Connect the positive supply (RED) wire to the screw terminal opposite the
preinstalled RED wire on the terminal block that connects to the back of the control
board.
b.
Connect the ground (BLACK) wire to the screw terminal opposite the preinstalled
BLACK wire on the terminal block that connects to the back of the control board.
Summary of Contents for OI-6000K NXP Series