INSTALLATION AND STARTUP
19
OI-6000K-X-X-X-NXP-X OPS_GUIDE_REV 1.0
2.3.6
CONNECTING THE FAULT TERMINAL
The fault terminal is used to provide indication of a device failure. The fault terminal is shipped
configured as a normally-closed (NC), or fail-safe, configuration, terminating power to the external
fault device when prompted, changing this behavior is detailed in the product settings and
configuration section of this manual. Unlike the optional relay terminals, the fault terminal is a
wet-contact, requiring only the power and ground wires of the external fault device to be wired
during installation. Refer to the following instructions for how to wire your device:
On the external fault device (light/horn):
1.
Locate the power (RED) and ground (BLACK) wires on the alarming device.
On the GEN II Model OI-6000K Detector:
1.
Feed the alarming device wires through a cord grip and into the enclosure.
2.
Locate the fault terminal block on the control board and complete the following:
a.
Connect the external fault device power (RED) wire to the “+” terminal.
b.
Connect the
external fault device ground (BLACK) wire to the “
-
” terminal.
EXTERNAL
FAULT DEVICE
OI-6000K
FAULT TERMINAL
PWR
RED
+
RED
GND
BLACK
-
BLACK