Covered Alcove:
spaces open only on one side and with an overhang
Horizontal Termination Clearances Continued:
Covered Alcove Application
Location
Country
Minimum Clearance
Description
CO
VE
RE
D
AL
CO
VE
A
PP
LI
CAT
IO
N
M
US &
Canada
24 inches
Clearance under
non-vinyl
veranda, porch, deck, balcony or overhang.
NOTE: Termination in a covered alcove space is permitted with the dimensions specified.
1. There must be 3 feet minimum between termination caps.
2. All mechanical air intakes within 10 feet of a termination cap must be a minimum of 3 feet
below the termination cap.
3. All gravity air intakes within 3 feet of a termination cap must be a minimum of 1 foot below
the termination cap.
42 inches
Clearance under
vinyl
veranda, porch, deck, balcony or overhang.
NOTE: Termination in a covered alcove space is permitted with the dimensions specified.
1. There must be 3 feet minimum between termination caps.
2. All mechanical air intakes within 10 feet of a termination cap must be a minimum of 3 feet
below the termination cap.
3. All gravity air intakes within 3 feet of a termination cap must be a minimum of 1 foot below
the termination cap.
N
US &
Canada
6 inches
Non-vinyl sidewalls.
12 inches
Vinyl sidewalls.
P
US &
Canada
8 feet
Alcove height.
Q
US &
Canada
See table below.
Alcove width (dependent on number of caps in the space).
R
US &
Canada
See table below.
Alcove depth (dependent on number of caps in the space).
# Vent Caps
Q
MINIMUM
R
MAXIMUM
1 vent cap
3 feet
2 x Q
ACTUAL
2 vent caps
6 feet
1 x Q
ACTUAL
3 vent caps
9 feet
2
/
3
x Q
ACTUAL
4 vent caps
12 feet
1
/
2
x Q
ACTUAL
Q
MIN
= # vent caps x 3
R
MAX
= (
2
/
# vent caps
) x Q
ACTUAL
HORIZONTAL TERMINATION CAP CLERANCES - NOTES:
If exterior walls are finished with vinyl siding, it is
required
that a vinyl protector kit be installed.
Vent system termination is not permitted in screened porches.
Vent system termination is permitted in porch areas with two or more sides open. You must follow all side walls, overhang
and ground clearances as stated.
Termination caps may be hot. Consider their proximity to doors or other traffic areas.
Summary of Contents for Clear 130 LS
Page 53: ...53 Wiring Diagram Screen Fireplace with Interior Lighting...
Page 54: ...54 Wiring Diagram Screen Fireplace with Interior Lighting and Ortal Power Vent...
Page 55: ...55 Wiring Diagram Double Glass Fireplace...
Page 56: ...56 Wiring Diagram Double Glass Fireplace with Interior Lighting...
Page 57: ...57 Wiring Diagram Double Glass Fireplace with Interior Lighting and Ortal Power Vent...
Page 58: ...58 Carbon Monoxide Detector Wiring Diagrams CO Kit Wiring Diagram Screen Fireplace...
Page 59: ...59 CO Kit Wiring Diagram Double Glass Fireplace...