IG-258-EN, version 02; 16/11/2018

4

Description and main characteristics 

General Instructions

ekor

.bat-200

1.  Description and main characteristics

1.1.  Definition

The 

ekor

.bat-200 unit is a 24 V

dc

 or 48 V

dc

 battery charger, 

depending on the model, for connection of units which 
feed 

Ormazabal

 cubicles.

1.2.  Architecture

The 

ekor

.bat-200 charger is a UPS where the battery is 

connected to the output, as shown in the image below.

1

Input

2

Output

3

10 kV insulation

4

Phase

5

Neutral

6

AC

7

DC

8

+ 24/48 V

dc

9

0 V

10

Earth

11

Chassis

12

Control

13

Alarms

14

Local signalling

15

Ethernet RS232

Figure 1.1. 

Unit architecture

1.3.  Processes

1.3.1.  Start-up and battery connection

When the unit is connected at 230 V

ac

, it is energised at this 

instant since the unit does not have an on switch. 

When the charger is energised, the initial PowerUP process 
extracts output voltage and checks that there are batteries 
connected; if there are, the internal contact closes, starting 
the battery charge process.

Summary of Contents for velatia ekor.bat-200

Page 1: ...LIB ekor bat 200 Battery Charger General Instructions IG 258 EN version 02 16 11 2018...

Page 2: ...ectrical installations Personnel must be fully familiar with the instructions and warnings contained in this manual and in other recommendations of a more general nature which are applicable to the si...

Page 3: ...t or Impedance measurement 6 2 Characteristics 7 2 1 Electrical characteristics 7 2 2 Dielectric strength 7 2 3 Service conditions 8 2 4 CE Conformity 8 3 Tests 9 3 1 ekor bat 200 battery charger 9 4...

Page 4: ...ut as shown in the image below 1 Input 2 Output 3 10 kV insulation 4 Phase 5 Neutral 6 AC 7 DC 8 24 48 Vdc 9 0 V 10 Earth 11 Chassis 12 Control 13 Alarms 14 Local signalling 15 Ethernet RS232 Figure 1...

Page 5: ...ge to vary by each degree centigrade The compensation range is limited between a maximum and minimum temperature comp_tmin and comp_tmax Temperature compensation hab_comp can also be enabled in fast c...

Page 6: ...ted and no more battery tests are carried out until this alarm is recognised The Battery failure alarm is grouped within the Urgent failure digital output 1 3 5 Fast test or Impedance measurement Thef...

Page 7: ...nt 20 A Power factor 0 6 Rated power 200 W Maximum power 500 W Output range 48 Vcc 39 60 24 Vcc 18 30 V Table 2 1 Input characteristics The charger has four potential free contacts Parameter Remarks V...

Page 8: ...requirements RoHS Directive 2002 95 CE Table 2 3 Service conditions For higher altitudes check with Ormazabal for the possible influence on equipment performance 2 4 CE Conformity This product compli...

Page 9: ...terminals of each unit differential mode 1 kV EN 60255 5 Immunity Level Standard Electrostatic discharge Direct contact mode in metal equipment frames and connectors Level 4 8 kV EN 6100 4 2 Air mode...

Page 10: ...nt peaks start up at rated power Level to be applied 12 A Mechanical tests Level Standard IP Protection grade Level to be applied IP20 EN 20324 IK Protection grade Level to be applied IK06 EN 50102 Vi...

Page 11: ...230 Vac rms 2 AC input N phase X2 Alarms 1 Urgent failure alarm NC contact 2 Standalone end alarm NA Contact 3 Power failure alarm NA Contact 4 Non urgent failure alarm NA Contact 5 Alarms common X3...

Page 12: ...d On Battery test failure end of battery s working life Red Charger ERROR Flashing Anomalies in charger Temperature sensor others On Temperature sensor failure Table 4 2 Description of the indications...

Page 13: ...button is pressed for more than 3 seconds If there is a battery connected the charge process continues and the battery test failure alarm resets if it is enabled If there is no battery the urgent alar...

Page 14: ...ETH1 port Access to the charger s webpage is via the ETH1 port both locally and remotely LOCAL IP 100 0 0 1 Remote IP Customised with the requested value Firefox browser version 26 is recommended for...

Page 15: ...ltage in fast charge V V comp_carga Temperature compensation in fast charge mV C hab_comp Enables temperature compensation in charge 0 NO 1 YES i_flot Battery through current to float mA tlim_carga Ma...

Page 16: ...esses IP Connexion IP for the SNTP protocol 20 char Gateway Gateway for the SNTP protocol SI_TFALL Time without synchronising in order to consider the internal clock out of sync min T_PETSINCRO Server...

Page 17: ...oved and all the meters and the state machine restart always maintaining voltage without any interruption in supply 7 2 Hardware test This window can be used to force the state of the luminous indicat...

Page 18: ...ery alarm is enabled meaning the urgent failure output and the Battery ERROR LED will be enabled 4 Position new batteries and make connections between them 5 Check that battery voltage is between 42 V...

Page 19: ......

Page 20: ...Subject to change without prior notice For further information contact Ormazabal Ormazabal Protection Automation IGORRE Spain www ormazabal com...

Reviews: