Ormazabal velatia ekor.bat-200 General Instructions Manual Download Page 12

IG-258-EN, version 02; 16/11/2018

12

Connections 

General Instructions

ekor

.bat-200

4.2.  LED indications

The charger has eight light indicators. Some of these can 
show double signalling. The indications only use a flashing 
frequency.

LED

Text 

Mode 

Associated function

Green

Power ON

On

Charger running on battery or network

Green

Battery charging

Flashing 

Charge mode: Fast. (Constant voltage)

On

Charge mode: Floating

Green

Battery test

On

Working battery test

Yellow

Battery discharging

On

Battery discharging

Red

V

AC

 IN ERROR

Flashing 

Network input outside of permitted margins

Red

V

DC

 OUT ERROR

Flashing 

24/48 V

dc

 output outside of permitted margins

Red

Battery ERROR

Flashing 

 Absence of battery, battery disconnected

On

Battery test failure, end of battery's working life

Red

Charger ERROR

Flashing 

Anomalies in charger. Temperature sensor, others…

On

Temperature sensor failure

Table 4.2. 

Description of the indications by LED

4.3.  Alarms

Name

Logic

Input network failure

The contact is open in normal operation.
It closes if AC voltage input is out of range, or there is an absence of AC voltage.

Urgent charger-rectifier failure  

The contact is open in normal operation.
It closes if:
•  There is no battery connected.
•  Battery Test Failure.
•  Urgent internal failures.
•  Charger temperature out of range.

Non-urgent charger-rectifier failure 

The contact is open in normal operation.
It closes if:
•  Max battery voltage
•  Temperature sensor error
•  Output voltage out of range.
•  Battery temperature out  range.

End of battery life

The contact is open in normal operation.
It closes if battery voltage drops below minimum discharge voltage.

Table 4.3. 

Alarms

Summary of Contents for velatia ekor.bat-200

Page 1: ...LIB ekor bat 200 Battery Charger General Instructions IG 258 EN version 02 16 11 2018...

Page 2: ...ectrical installations Personnel must be fully familiar with the instructions and warnings contained in this manual and in other recommendations of a more general nature which are applicable to the si...

Page 3: ...t or Impedance measurement 6 2 Characteristics 7 2 1 Electrical characteristics 7 2 2 Dielectric strength 7 2 3 Service conditions 8 2 4 CE Conformity 8 3 Tests 9 3 1 ekor bat 200 battery charger 9 4...

Page 4: ...ut as shown in the image below 1 Input 2 Output 3 10 kV insulation 4 Phase 5 Neutral 6 AC 7 DC 8 24 48 Vdc 9 0 V 10 Earth 11 Chassis 12 Control 13 Alarms 14 Local signalling 15 Ethernet RS232 Figure 1...

Page 5: ...ge to vary by each degree centigrade The compensation range is limited between a maximum and minimum temperature comp_tmin and comp_tmax Temperature compensation hab_comp can also be enabled in fast c...

Page 6: ...ted and no more battery tests are carried out until this alarm is recognised The Battery failure alarm is grouped within the Urgent failure digital output 1 3 5 Fast test or Impedance measurement Thef...

Page 7: ...nt 20 A Power factor 0 6 Rated power 200 W Maximum power 500 W Output range 48 Vcc 39 60 24 Vcc 18 30 V Table 2 1 Input characteristics The charger has four potential free contacts Parameter Remarks V...

Page 8: ...requirements RoHS Directive 2002 95 CE Table 2 3 Service conditions For higher altitudes check with Ormazabal for the possible influence on equipment performance 2 4 CE Conformity This product compli...

Page 9: ...terminals of each unit differential mode 1 kV EN 60255 5 Immunity Level Standard Electrostatic discharge Direct contact mode in metal equipment frames and connectors Level 4 8 kV EN 6100 4 2 Air mode...

Page 10: ...nt peaks start up at rated power Level to be applied 12 A Mechanical tests Level Standard IP Protection grade Level to be applied IP20 EN 20324 IK Protection grade Level to be applied IK06 EN 50102 Vi...

Page 11: ...230 Vac rms 2 AC input N phase X2 Alarms 1 Urgent failure alarm NC contact 2 Standalone end alarm NA Contact 3 Power failure alarm NA Contact 4 Non urgent failure alarm NA Contact 5 Alarms common X3...

Page 12: ...d On Battery test failure end of battery s working life Red Charger ERROR Flashing Anomalies in charger Temperature sensor others On Temperature sensor failure Table 4 2 Description of the indications...

Page 13: ...button is pressed for more than 3 seconds If there is a battery connected the charge process continues and the battery test failure alarm resets if it is enabled If there is no battery the urgent alar...

Page 14: ...ETH1 port Access to the charger s webpage is via the ETH1 port both locally and remotely LOCAL IP 100 0 0 1 Remote IP Customised with the requested value Firefox browser version 26 is recommended for...

Page 15: ...ltage in fast charge V V comp_carga Temperature compensation in fast charge mV C hab_comp Enables temperature compensation in charge 0 NO 1 YES i_flot Battery through current to float mA tlim_carga Ma...

Page 16: ...esses IP Connexion IP for the SNTP protocol 20 char Gateway Gateway for the SNTP protocol SI_TFALL Time without synchronising in order to consider the internal clock out of sync min T_PETSINCRO Server...

Page 17: ...oved and all the meters and the state machine restart always maintaining voltage without any interruption in supply 7 2 Hardware test This window can be used to force the state of the luminous indicat...

Page 18: ...ery alarm is enabled meaning the urgent failure output and the Battery ERROR LED will be enabled 4 Position new batteries and make connections between them 5 Check that battery voltage is between 42 V...

Page 19: ......

Page 20: ...Subject to change without prior notice For further information contact Ormazabal Ormazabal Protection Automation IGORRE Spain www ormazabal com...

Reviews: