IG-258-EN, version 02; 16/11/2018
7
General Instructions
ekor
.bat-200
Characteristics
2. Characteristics
This section describes the main characteristics of the
ekor
.bat-200 unit.
2.1. Electrical characteristics
The characteristics of the
input
are as follows:
Parameter
Remarks
Value
Unit
Rated input voltage
230
V
ac
Input voltage range
160…300
V
ac
Input frequency range
Compatible with 50/60 Hz
50…60
Hz
Start-up current
< 20
A
Power factor.
> 0.6
Rated power
200
W
Maximum power
500
W
Output range
48 V
cc
= 39..60
24 V
cc
= 18..30
V
Table 2.1.
Input characteristics
The charger has four
potential-free contacts
.
Parameter
Remarks
Value
Unit
Rated Voltage
24 / 48
V
dc
Maximum current
100
mA
Table 2.2.
potential-free contacts
2.2. Dielectric strength
The unit withstands dielectric rigidity tests at a leakage
current of < 10 mA for the voltage indicated during 1
minute between the following parts:
• Input vs. ( Temp. Communic.
+ Earth) = 10 kV
AC
( Temp. Sensor) vs. Earth =
2500 V
AC
• Alarms vs. Earth = 1000 V
AC
• Communications vs. Earth = 1000 V
AC