Metering function and auxiliary services
Figure 4.13.
Cable trench dimensions [mm] for
cgmcosmos
-ma
Trench necessary for the metering function and auxiliary services
Cable insulation
Cable type
Cable
section
[mm
2
]
Cable
diameter
[mm]
Approximate
radius of
curvature*
[mm]
Minimum depth
D2
Height
1800 mm
Dry insulation
Single-phase
< 150
41
555
600
185
43
590
650
240
45.2
640
700
300
47.5
685
750
400
50.5
745
800
* Check against the data of the manufacturer of the cable used.
Table 4.11.
Trench necessary for the function
IG-078-EN version 12; 23/04/2020
30
Installation
General Instructions
cgmcosmos
: Medium-voltage cubicles with full insulation
in SF
6
gas up to 24 kV in accordance with IEC Standard
Summary of Contents for velatia cgmcosmos