Metering function and metering with earthing switch
Dimensions in mm.
Figure 4.12.
Dimensions [mm] of the cable trench for
cgmcosmos
-m
Trench required for the metering function and metering with earthing switch
Cable insulation
Cable type
Cable
section
[mm
2
]
Cable
diameter
[mm]
Approximate
radius of
curvature*
[mm]
Minimum depth
D2
Height
1740 mm
Dry insulation
Single-phase
< 150
41
555
600
185
43
590
650
240
45.2
640
700
300
47.5
685
750
400
50.5
745
800
* Check against the data of the manufacturer of the cable used.