background image

SMTS II for GPC-XP Technical Guide

 

         

GPC-XP CONTROLLER SCREENS

15

Figure 22:   Relay Output Force Mode Screen

Figure 26:  Outdoor and AVC Status Screen

Figure 27:  Schedules and Holidays Screen

Figure 23:   Analog Outputs Screen

Figure 24:   Analog Output Detail Screen

Figure 25:  Analog Output Force Screen

Relay Output Force Modes, Analog Outputs, and Analog Force

 Relay Force: 

You can now 

select 

the radio button for the force 

mode—Normal Operation, Force Relay On, or Force Relay Off.

 

 

Runtime Reset: 

You can also 

touch

 the Runtime Hrs and Runtime 

Minutes data fi eld to reset Runtimes (

Figure 21

).

Analog Outputs:  

From the 

Analog Outputs Screen

 (

Figure 23

you can access the detail screen by 

selecting

 one of the data fi elds. 

In the example below (

Figure 24

), Tower Fan Speed is selected. 

 Force Analog Output: 

From the 

Analog Output Detail Screen

 

(

Figure 24

), you can access the 

Force Screen

 (

Figure 25

 above) 

by 

selecting

 the Force Value data fi eld. 

Enter

 a percentage between 

0 and 100. 

Enter

 -1 to Cancel the Force Mode.

 Outdoor and  AVC Status:  

This screen (

Figure 26

) is for view-

ing only. 

 Schedules & Holidays:  

Refer to the next section for instructions. 

Summary of Contents for OE392-10-GPCXP

Page 1: ...System Manager TS II For GPC XP Technical Guide GPC XP Controller Code YS102432 Revision 4 0 and up ...

Page 2: ...wing and Setting Holidays 17 Schedule Override 18 ALARMS 18 Viewing Enabling Disabling Alarms 18 APPENDIX 19 Troubleshooting System Manager TS II LEDs Buttons Dipswitches and Jumpers 19 Military Time Conversion 20 INDEX 21 WattMaster Controls Inc 8500 NW River Park Drive Parkville MO 64152 Toll Free Phone 866 918 1100 PH 816 505 1100 FAX 816 505 1101 E mail mail wattmaster com Visit our web site a...

Page 3: ...amming Comes equipped with real time clock backup power supply for short power losses Provides icons to indicate alarm conditions LEDs behind plastic panel indicate power communica tions and operation Plastic enclosure allows for easy flush wall mounting in hollow drywall or surface mounting on solid wall surface System Manager TS II System Requirements The System Manager TS II is packaged and ass...

Page 4: ...arily freeze the touch pad before you attempt to clean your screen See the Troubleshooting section on page 19 for details Wiring The System Manager TS II is connected to the local communications loop of the Orion system via 18AWG 2 conductor twisted pair with shield wire connected to the T SHLD R communication terminals on the back of the System Manager TS II The communications wire used can be ei...

Page 5: ...SMTS II for GPC XP Technical Guide COMPONENTS WIRING 5 Flush Wall Mount Dimensions and Components Figure 3 System Manager TS II Dimensions and Components Flush Wall Mount ...

Page 6: ...COMPONENTS WIRING SMTS II for GPC XP Technical Guide 6 Surface Mount Dimensions and Components Figure 4 System Manager TS II Dimensions and Components Surface Mount ...

Page 7: ...niLink s Both Jumpers Must Be OFF OFF OPT4 OPT3 OPT2 OPT1 SW1 NOTE Dip Switch OPT1 Should Be Set To ON When GPC XP Is Set To High Speed OPT2 OPT3 As Of April 2014 OPT4 Should Be Set To ON By Default Previous Versions Should Be Set To OFF If You See Your Screen Is Not Centered Correctly Switch OPT4 To The Opposite Position Should Be Set To OFF COM FROM GND CUT TO ISOLATE WATTMASTER CONTROLS YS10243...

Page 8: ...ion System settings are only accessible to a Level 3 user The Set Time Date icon takes you to the Set Time and Date Screen Any level of user can set the time and date Navigation Buttons See Table 2 for a list of Navigation buttons and their functions Button Function Back Use the Back button while in a Data Entry Screen to return to the Status Screen Use the Back button while in a Status Screen to ...

Page 9: ...to the Touch Screen while the GPC XP is initializing This can cause programming errors Main Screen Once you have connected your System Manager TS II to a control ler and have powered it up with the proper power supply the Main Screen will appear See Figure 6 Figure 7 Login Screen Enter the 4 digit Passcode for the required Level Level 1 Can change space setpoints Level 2 Can change schedules Level...

Page 10: ...en will appear See Figure 8 To change a passcode touch the blue highlighted box containing the current passcode The keypad will appear with instructions for changing the passcode See Figure 9 The current passcode will appear on the top menu bar Type in the new four digit passcode You cannot use the period or minus char acters in your passcode Use the key if you make a mistake Touch Esc to return t...

Page 11: ...When you are finished setting the clock touch the Broadcast button to broadcast the Time and Date to all Units The following message will appear Figure 10 Set Time Date Screen Back Set Time Date Broadcast System Manager Settings Mon Tue Wed Hour Minute Month Day Year 14 12 1 16 14 Sun Thu Sun Thu Fri Sun Fri Sat Sun Sat Esc 1 2 3 4 7 0 9 8 5 6 OK Currently 10 DATA ENTRY Set Clock Hour Enter the Cu...

Page 12: ...t using a CommLink or MiniLink anywhere on the loop your system is Stand Alone If your System Manager TS II is connected to more than one controller daisy chained together and you are not using a CommLink or MiniLink anywhere on the loop your system is Interconnected If you have either a Stand Alone or Interconnected system you must enter 0 for Stand Alone Mode In order to view all controllers on ...

Page 13: ... Status Screens and corresponding data entry screens associated with them Notice that the controller is identified by loop number and unit number in this case 0001 represents Unit 1 with a stand alone connection Figure 14 Analog Inputs Screen While in each Status Screen touch the and buttons to view more status screens These screens roll back to the first Status Screen Figure 15 Analog Input Detai...

Page 14: ... operation To do this while in the Relay Outputs Screen Figure 20 touch the value field for the Relay you would like to force on or off In the example below Figure 21 Relay Output 5 Tower Fan is selected Touch the Tower Fan s data field The Relay Output Force Mode Screen will appear Figure 22 Figure 21 Relay Output Details Screen Analog Inputs Binary Inputs and Relay Outputs Override Reading To ov...

Page 15: ...e Relay Off Runtime Reset You can also touch the Runtime Hrs and Runtime Minutes data field to reset Runtimes Figure 21 Analog Outputs From the Analog Outputs Screen Figure 23 you can access the detail screen by selecting one of the data fields In the example below Figure 24 Tower Fan Speed is selected Force Analog Output From the Analog Output Detail Screen Figure 24 you can access the Force Scre...

Page 16: ...be entered in military time format See the Military Time Table in the Appendix page 20 Touch OK to save the time you entered or touch Esc to exit the Schedule Times Screen without changing the time and return to the Week Schedules Screen Figure 29 To eliminate a schedule from any event simply enter a zero for the Start and Stop time for that day The screen will display 12 00 am for both the Start ...

Page 17: ...he NORMAL button for the desired Schedule The Holidays Schedule Screen will appear starting with the current month and year See Figure 32 Figure 32 Holidays Schedule Screen Figure 31 Status Screen 6 Schedules The holidays in the screen will initially not be set You can only set holidays for the current year Simply touch the day s of the month to select holidays Touch the button to go back one mont...

Page 18: ...sly Prism 2 does have to be running for emailing or texting alarms to occur To enable an alarm simply touch the gray square next to each alarm Awhite box designates that the alarm is enabled To disable the alarm simply touch the square again A gray box designates that the alarm category is disabled When an alarm is enabled and there is no alarm condition the word OK appears in a box next to the ty...

Page 19: ...ols Technical Support you may have to perform diagnostics on your System Manager TS II Press this button to do so Touch Screen Suspend Button Press this button to temporarily freeze the touch screen function of your System Manager TS II in order to clean the screen Always use a dry dust free cloth to clean the screen OPT1 Dipswitch OPT1 Dipswitch should be ON if the GPC XP is set to High Speed Thi...

Page 20: ...early identify the time of day Since military time uses a unique two digit number to identify each of the 24 hours in a day a m and p m are unnecessary The following table summarizes the relationship between regular and military time Regular Time Military Time 12 00 a m 0000 12 30 a m 0030 1 00 a m 0100 1 30 a m 0130 2 00 a m 0200 2 30 a m 0230 3 00 a m 0300 3 30 a m 0330 4 00 a m 0400 4 30 a m 04...

Page 21: ...s 8 Icons 8 Diagnostics Button 19 Dimensions 5 Dipswitch Settings 4 Down Arrow Key Function 8 E Edit Passcodes 10 Environmental Requirements 4 Esc Key Function 8 F Features 3 Flush Wall Mount 4 5 Force Analog Output 15 Force Modes 17 G GPC XP Alarms Configuring 18 Enabling Disabling 18 GPC XP Controller Wiring to SMTS 7 GPC XP Controller Alarm Status Screen 18 H Holidays 17 Setting 17 Viewing 17 H...

Page 22: ...ed 8 SEND TO All Days 16 SEND TO Weekdays 16 Sensor Override Data Entry Screen 14 SET 24 Hr Mode 16 Set Clock Hour 11 Set Time and Date 11 Set Time Date Icon Description 8 Set Time Date Screen 11 Settings Icon Description 8 Setting the System Clock 11 Stand Alone 12 Surface Mount 6 Suspend Button 4 19 System Manager Address 12 System Manager Passcode 9 System Manager Passcode Levels Screen 10 Syst...

Page 23: ...SMTS II for GPC XP Technical Guide NOTES 23 ...

Page 24: ...SMTSII GPCXP TGD 01A Printed in the USA May 2014 All rights reserved Copyright 2014 WattMaster Controls Inc 8500 NW River Park Drive Parkville MO 64152 Phone 866 918 1100 www orioncontrols com Fax 816 505 1101 ...

Reviews: