Network Shutdown Module V3 

User Manual 

 

 

 

 

 

 
 
 
 

 
 
 
 

 

 
 

Network Shutdown Module V3 – User Manual - 34 003 896 XU / AE 

 

Содержание Network Shutdown Module V3

Страница 1: ...www eaton com Network Shutdown Module V3 User Manual Network Shutdown Module V3 User Manual 34 003 896 XU AE...

Страница 2: ...Procedure 12 2 5 Application deployment and silent installation advanced 14 2 6 Uninstalling the Network Shutdown Module 14 3 Minimal configuration steps 15 3 1 Introduction 15 3 2 The IP address of t...

Страница 3: ...ional information on events and actions 46 7 8 1 Action settings Tab 46 7 8 1 1 The different actions 46 7 8 1 2 Add an action 47 7 8 1 3 System Shutdown Action 47 7 8 1 4 Execute Action 49 7 8 1 5 Se...

Страница 4: ...ply of power to the computers connected to your computer network z carries out automatic shutdown of computer systems z monitors and controls all the UPSs connected to the network As illustrated in th...

Страница 5: ...ment Proxy Management Card and Shutdown Module include a Web server your company s standard Network Management System HP Openview CA Unicenter HP Insight Manager IBM Tivoli Netview To simplify integra...

Страница 6: ...ions The Network Shutdown Module V 3 20 offers the mass configuration advanced management feature through Enterprise Power Manager 2 20 The version V3 of the Network Shutdown Module z offers a remote...

Страница 7: ...ell as local protection of the machine on which Proxy is installed z periodically accesses the information concerning the UPS z makes this information available to the connected applications Network S...

Страница 8: ...TCP IP communication network 1 4 3 Network Performances The Network Management Card is designed to support a maximum of z 35 Network Shutdown Module connections in standard secure mode z 100 connectio...

Страница 9: ...installation manual z Connect the power cord of each computer to an outlet on the UPS For UPSs above 3kVA please refer to the UPS installation manual z How to connect UPS proxy or card network If the...

Страница 10: ...er Intel Xeon single processor for HS20 type 8843 Windows Server 2003 2 2 1 2 Linux Compatibilities Network Shutdown Module V3 Linux is compatible and has been tested with z Linux x86 x86_64 Debian GN...

Страница 11: ...t Assigned Numbers Authority http www iana org If you use Windows the ports are automatically opened in the Windows Firewall If you use a Firewall with all ports closed by default To enable communicat...

Страница 12: ...ows Firewall z Step 3 Software Installation On a Windows 2000 XP 2003 2008 Vista 7 Linux or Mac OSX machine execute the Network Shutdown Module package under an administrator account z Step 4 Configur...

Страница 13: ...or Lin nd save the file to your computer ckage through graphical interface ux From the web z Download a z Authorize the execution right on the downloaded pa or execute the command chmod 755 nsm_linux_...

Страница 14: ...ly started z It is possible to test Network Shutdown Module z The protection function is now active on the computer and will be run automatically each time the computer is started Follow these steps t...

Страница 15: ...2 6 Uninstalling the Network Shutdown Module Windows z The shortcut EATON Network Shutdown Module Uninstall is used to uninstall Network Shutdown Module or z In the Control panel you can also run the...

Страница 16: ...Proxy or use the following new function New With the Quick Scan button available with version 3 10 and later you can discover in a few seconds the cards connected to the network and then select a car...

Страница 17: ...powershare outlets Remark This load shedding function is not available if the UPS doesn t have any switchable outlet Note For multi UPS configurations you have the possibility to enter several names o...

Страница 18: ...create a new login with new access password User accounts configuration You can configure several user accounts To add a user account z enter the User Login and the User password twice z select the Us...

Страница 19: ...us 4 1 2 Remote access z From a remote machine you can type the following URL in a Web browser for secured SSL access https name or IP address of computer hosting NSM 4680 or for non secured access ht...

Страница 20: ...sting the Network Shutdown Module These values can be configured in the System page Section concerning the UPS that powers the protected server z This icon represents the status of the power device It...

Страница 21: ...ailure On Automatic Bypass Manual By Pass Overload Or output outlet status ON OFF The outlet group that powers the device is highlighted in bold Values z Output Load Level The output load level of the...

Страница 22: ...the Export button to record the displayed data into a CSV file z Use the Clear button to clear the displayed data 4 3 UPS Events list The icons in the Status view represent the event severity Icon Eve...

Страница 23: ...Critical A serious problem has occurred on the device This problem requires an urgent action Your application might NOT BE powered anymore Event list z UPS output is off z Battery fault z UPS overloa...

Страница 24: ...nstant then check the communication parameters between the computer and the Cards Proxy The Acquisition Engine is stopped Check in the services list that the service is started Battery fault Contact t...

Страница 25: ...bugMode on restart the EATON Network Shutdown Module Acquisition engine as explained hereafter 4 5 Start and stop the Shutdown Module advanced Warning if you stop your computer is not protected anymor...

Страница 26: ...on Status page Alarm reception mode In this area you can z Authorize UDP and TCP modes default value The Network Shutdown Module will thus determine automatically which mode is supported by the card a...

Страница 27: ...role of this parameter is illustrated by the example of shutdown sequence Possible values 0 to 9999 Default value 120 Unit Second It is on the basis of these values shutdown duration of all the system...

Страница 28: ...to administrators connected to the server protected by Network Shutdown Module Check following Windows pre requisite Default value activated z Message broadcast to users A message is sent over the net...

Страница 29: ...eration will preserve your database information Check for upgrade window 5 5 Events and actions advanced configuration Basic principles Network Shutdown Module receives events e g Utility Failure from...

Страница 30: ...y necessary if you require your protection module to operate in a particular way The default configuration ensures optimal protection of your installation Modifying parameters must therefore be done w...

Страница 31: ...ers before installing Network Shutdown Module 6 2 Presentation With the latest version V3 the Network Shutdown Module manages multi UPS redundant configurations The Network Shutdown Module V3 makes it...

Страница 32: ...utdown Module please refer to the appendix List of tested multi UPS configurations The Network Shutdown module doesn t take into account the real electrical drawing It computes dynamically the minimal...

Страница 33: ...capacity the battery capacity for the global installation z Global estimated backup time the remaining backup time for the global installation This value takes into account UPS load balancing anticip...

Страница 34: ...Select the Redundancy type of your installation Parallel STS Sequential Serial Server with multiple power supplies according to your electrical configuration Note For the Hot Standby Sequential UPS M...

Страница 35: ...t 66244 z Network Management Proxy V5 7 1 2 UPSs compatibility In Single UPS Mode the following UPSs are compatible through the Cards Proxy z Pulsar Pulsar M EX z Pulsar Extreme C z Pulsar Comet EXtre...

Страница 36: ...equential redundancy z 2 UPSs in serial redundancy Single Phase Pulsar Pulsar M EX Pulsar Extreme C Evolution z 2 UPSs through Static Transfer Switch Single Phase Pulsar Pulsar M EX Comet EXRT Pulsar...

Страница 37: ...hout synchro Pulsar Extreme C Pulsar M EX STS 16A without synchro Notes z This configuration has also been tested with 3 STSs z The Network Shutdown Module V3 is NOT compatible with a configuration wh...

Страница 38: ...ion with STS in cascade is NOT supported by NSM V3 z This configuration with a load derived between the 2 UPSs in serial redundancy is NOT supported by NSM V3 z This configuration with a mix of Parall...

Страница 39: ...t 25 1 2 UPSs of 1500 VA and a server with redundant power supply Each UPS loaded at 60 2 2 UPSs of 3000 VA in hot standby configuration 1 UPS loaded at 33 1 UPS loaded at 0 1 2 UPSs 30 KVA parallel r...

Страница 40: ...ti UPS system or you don t use Network Shutdown Module default configuration z Step 1 Install Network Shutdown Module on a computer interactive or silent mode z Step 2 Configure Network Shutdown Modul...

Страница 41: ...r local EATON NetworkShutdownModule z Execute the package standard installation or Silent installation Important z For Repackaging function If you are running Debian Sarge Redhat 3 4 Mandriva 2010 SLE...

Страница 42: ...e process It is possible to test Network Shutdown Module Example of secured deployment script for Linux We use ssh to copy the package on several machines and then execute it The script iterates on th...

Страница 43: ...tdown procedure The procedure is launched if 1 the shutdown time delay in seconds started when the loss of AC power occurred expires 2 the UPS battery level drops below a threshold expressed in 3 the...

Страница 44: ...Network Shutdown Module V3 User Manual 34 003 934 XU AE Page 43 65 Shutdown condition Maximum shutdown duration Utilityfailure Utility Output Network Management Card Sequence Utilityrestored 1 2 3 Sh...

Страница 45: ...e None 100 sec Shutdown duration 120 sec 180 sec 60 sec The main output shutdown duration is equal to 180 sec It is the shutdown duration of the machine 2 maximum of all the shutdown duration Shutdown...

Страница 46: ...e Static Transfer Switch balances the load on the second UPS Then we are in a typical single UPS sequence 3 z The Mgt Card launches the shutdown procedure for UPS 2 z As a result each Network Shutdown...

Страница 47: ...ts tab you can associate the selected action with the event s that will be able to trigger the action z In the Test tab you can execute the action by simulating the event occurrence z The Restore to d...

Страница 48: ...rver protected by Network Shutdown Module Note This action only occurs if the Administrator notification box is checked on the Configuration Network Shutdown Module screen System shutdown System and U...

Страница 49: ...is also de energized When mains power returns all the applications re open exactly as they were and the user finds himself back in his work environment The hibernate function must first have been acti...

Страница 50: ...n unique action identifier z Type Select Execute z Command line Fill in the command line the Browse button will help you find the path of the program to be executed The following utilities are supplie...

Страница 51: ...z Recipient Enter the e mail address To send the message to several recipients separate their addresses by a comma or semi colon z The Sender Subject and Message fields can be customized as above Not...

Страница 52: ...p is displayed when the mouse pointer is positioned over it Following events can trig the actions They are classed by category 7 8 2 1 Notification alarms These alarms are mainly dedicated to trigger...

Страница 53: ...re a Shutdown action when a Notification Alarm event is received In this case z The first alarm reception from one of the UPSs will trigger the system shutdown 7 8 2 4 Multi UPS Systems and Protection...

Страница 54: ...AE Page 53 65 7 8 3 Test tab In the Test tab you can execute the action by simulating the event occurrence You can select the event Warning This action will be really executed Check that you re ready...

Страница 55: ...wn Module host card_proxy Send Network Management Card Proxy name or IP address hostname Send Network Shutdown Module host name or IP address 7 8 5 Software utilities The following utilities are suppl...

Страница 56: ...tion directory Program Files EATON NetworkShutdownModule bin tools z Use The parameter for the program is the time delay expressed in milliseconds z Example Wait exe 2000 The system will wait for two...

Страница 57: ...mmand to be run using the specified account 3 Click the Generate button 4 Copy the command line and paste it in your application This line may be used as it is in a Network Shutdown Module Run action...

Страница 58: ...mporary file eatonInstall xml is not removed z This file is created in the directory where you execute the installer Solution At the end of installation you can remove manually the file During use Lin...

Страница 59: ...11 On these platforms just after Installation and configuration the NSM has sufficient user rights to build the customized package After a computer reboot the NSM doesn t have sufficient user rights t...

Страница 60: ...Check the URL entered https name or IP address of computer hosting NSM 4680 or http name or IP address of computer hosting NSM 4679 When you attempt to view the properties or configuration pages the b...

Страница 61: ...ied to the computer If the supply of the electrical power from the EATON UPS is at risk the Network Shutdown Module initiates an orderly shutdown of the computer under the most secure conditions possi...

Страница 62: ...INCLUDING BUT NOT LIMITED TO PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES LOSS OF USE DATA OR PROFITS OR BUSINESS INTERRUPTION HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY WHETHER IN CONTRACT STRICT L...

Страница 63: ...e at http www zend com 9 4 OpenSSL Huge thanks from the EATON software development team to the OpenSSL Project OpenSSL License Copyright c 1998 2006 The OpenSSL Project All rights reserved Redistribut...

Страница 64: ...ith or without modification are permitted provided that the following conditions are met 1 Redistributions of source code must retain the copyright notice this list of conditions and the following dis...

Страница 65: ...nt but changing it is not allowed WXWINDOWS LIBRARY LICENCE TERMS AND CONDITIONS FOR COPYING DISTRIBUTION AND MODIFICATION This library is free software you can redistribute it and or modify it under...