32
9
SPECIFICATIONS
9.1
120V
Model number
750/1000VA 1500VA
2200VA
3000VA
Power Rating, VA/W
750VA/750W
1000VA/900W
1500VA/1350W 1920VA/1920W 3000VA/2700W
Dimensions, W x D x H, in
Unit
3.5”(2U) H x
18”W x
17”D
3.5”(2U) H x
18”W x
17”D
3.5”(2U) H x
18”W x
26”D
3.5”(2U) H x
18”W x
26”D
Weight, lbs
Unit 45
48
77
85
Input AC Parameters
Surge Protection
570J
Voltage Range
Without
Battery Operation
83~159, configurable
Frequency Range
45~65Hz, (±0.5Hz)
Input Power Cord
10ft(3m)
attached,
w/ NEMA 5-15P
10ft(3m)
attached,
w/ NEMA 5-15P
10ft(3m)
attached,
w/ NEMA 5-20P
10ft(3m) attached,
w/ NEMA L5-30P
Output Receptacles
(8) NEMA 5-15R
(8) NEMA 5-15R
(6) NEMA 5-15R
(2) NEMA 5-20R
(6) NEMA 5-15R
(2) NEMA 5-20R
(1) NEMA L5-30R
Voltage (Normal
mode)
110 / 120 / 127 VAC (configurable) ±10%
Voltage (Battery
Mode)
110 / 120 / 127 VAC (configurable);
±5% before low battery warning
Transfer Time
4-6 ms typical
Waveform Sinewave
Frequency
(Normal Mode)
45~65Hz, (±0.5Hz)
Frequency
(Battery Mode)
50/60Hz, (±0.5Hz), auto sensing
Overload Warning
>100% - 109%
Continuous Overload Alarm and power to the load
>110% - 120%
Shutdown after 10 minutes
Normal Mode
>120%
Shutdown UPS immediately
>100% - 119%
Continuous Overload Alarm till end of battery discharged
>120% - 130%
Shutdown after 10 seconds
Battery Mode
>130%
Shutdown UPS immediately
Battery Parameters
Type
Valve-regulated, nonspillable, lead acid
33
Backup Time *
1000VA
1500VA
2200VA
3000VA
Full Load 7m
5m
5m
5m
Half Load
19m
16m
16m
16m
Recharge Time
5 hours to 90% of rated capacity, after full discharge into resistive load
Environmental
Operating
Temperature
+32°F to + 104°F (0°C to + 40°C)
Storage Temperature
+5°F to + 104°F (-15°C to + 40°C)
Relative Humidity
0% to 95%, non-condensing
Operating Altitude
Up to 10,000 ft. (3000m) at 95°F (35°C) without derating
Audible Noise
<40 dBA, internal fan(s) Off
<45 dBA, internal fan(s) On
<40 dBA, internal fan(s) Off
<45 dBA, internal fan(s) On
Agency
Safety
UL 1778, c-UL Listed
Surge
ANSI C62.41 CatA Lev3 (surges)
IEC61000-4-5
ESD IEC61000-4-2
Susceptibility IEC61000-4-3
Electrical Fast
Transient
IEC61000-4-4
Emissions
FCC Part 15, Class A
Conducted Immunity
EN61000-4-6
Harmonics EN61000-3-2
Network surge
UL 497 B
Transportation
ISTA Procedure 1A Certification
*
Runtimes reflect .7 power factor and are approximate. Run times may vary depending on
battery age, temperature, etc.